SPEC: 45043

Southwire® Machine Flex® CU 600/1000V PVC-Nylon Insulation THHN TPE Black Jacket. Silicone-Free SPEC45043

Type TC-ER Machine Tray Power Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4. Silicone-Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s Machine Flex® tray power cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Southwire’s machine tray cable is ideal to power CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind energy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) AC Resistance at 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
18 AWG 18 AWG
3 3
16 16
0.044 0.11
20 0.51
45 1.14
0.281 0.71
15 22
43 64
8.613 12.82
1.1 2.79
- -
14 14
More Options
18 AWG 18 AWG
4 4
16 16
0.044 0.11
20 0.51
45 1.14
0.306 0.78
20 30
54 80
8.613 12.82
1.2 3.05
- -
11 11
More Options
18 AWG 18 AWG
5 5
16 16
0.044 0.11
20 0.51
45 1.14
0.332 0.84
25 37
63 94
8.613 12.82
1.3 3.30
- -
11 11
More Options
18 AWG 18 AWG
6 6
16 16
0.044 0.11
20 0.51
45 1.14
0.348 0.88
30 45
84 125
8.613 12.82
1.4 3.56
- -
11 11
More Options
18 AWG 18 AWG
7 7
16 16
0.044 0.11
20 0.51
45 1.14
0.358 0.91
35 52
80 119
8.613 12.82
1.4 3.56
- -
9 9
More Options
18 AWG 18 AWG
8 8
16 16
0.044 0.11
20 0.51
45 1.14
0.401 1.02
40 60
111 165
8.613 12.82
1.6 4.06
- -
9 9
More Options
18 AWG 18 AWG
9 9
16 16
0.044 0.11
20 0.51
45 1.14
0.411 1.04
45 67
102 152
8.613 12.82
1.6 4.06
- -
9 9
More Options
18 AWG 18 AWG
10 10
16 16
0.044 0.11
20 0.51
45 1.14
0.438 1.11
50 74
137 204
8.613 12.82
1.8 4.57
- -
7 7
More Options
18 AWG 18 AWG
12 12
16 16
0.044 0.11
20 0.51
45 1.14
0.456 1.16
60 89
132 196
8.613 12.82
1.8 4.57
- -
7 7
More Options
18 AWG 18 AWG
14 14
16 16
0.044 0.11
20 0.51
45 1.14
0.469 1.19
70 104
140 208
8.613 12.82
1.9 4.83
- -
7 7
More Options
18 AWG 18 AWG
16 16
16 16
0.044 0.11
20 0.51
45 1.14
0.495 1.26
80 119
165 246
8.613 12.82
2.0 5.08
- -
7 7
More Options
18 AWG 18 AWG
19 19
16 16
0.044 0.11
20 0.51
65 1.65
0.560 1.42
95 141
236 351
8.613 12.82
2.2 5.59
- -
7 7
More Options
18 AWG 18 AWG
25 25
16 16
0.044 0.11
20 0.51
65 1.65
0.635 1.61
125 186
254 378
8.613 12.82
1.3 3.30
- -
6 6
More Options
18 AWG 18 AWG
37 37
16 16
0.044 0.11
20 0.51
65 1.65
0.732 1.86
186 277
422 628
8.613 12.82
2.9 7.37
- -
5 5
More Options
16 AWG 16 AWG
2 2
26 26
0.059 0.15
20 0.51
50 1.27
0.311 0.79
16 24
48 71
5.406 8.05
1.2 3.05
- -
18 18
More Options
16 AWG 16 AWG
3 3
26 26
0.059 0.15
20 0.51
50 1.27
0.311 0.79
24 36
58 86
5.406 8.05
1.2 3.05
- -
18 18
More Options
16 AWG 16 AWG
4 4
26 26
0.059 0.15
20 0.51
50 1.27
0.339 0.86
32 48
71 106
5.406 8.05
1.4 3.56
- -
14 14
More Options
16 AWG 16 AWG
5 5
26 26
0.059 0.15
20 0.51
45 1.14
0.370 0.94
40 60
86 128
5.406 8.05
1.5 3.81
- -
14 14
More Options
16 AWG 16 AWG
6 6
26 26
0.059 0.15
20 0.51
50 1.27
0.462 1.17
48 71
140 208
5.406 8.05
1.9 4.83
- -
14 14
More Options
16 AWG 16 AWG
7 7
26 26
0.059 0.15
20 0.51
50 1.27
0.400 1.02
56 83
122 182
5.406 8.05
1.6 4.06
- -
12 12
More Options
16 AWG 16 AWG
8 8
26 26
0.059 0.15
20 0.51
50 1.27
0.431 1.09
64 95
142 211
5.406 8.05
1.7 4.32
- -
12 12
More Options
16 AWG 16 AWG
9 9
26 26
0.059 0.15
20 0.51
50 1.27
0.462 1.17
72 107
138 205
5.406 8.05
1.9 4.83
- -
12 12
More Options
16 AWG 16 AWG
10 10
26 26
0.059 0.15
20 0.51
50 1.27
0.509 1.29
81 121
153 228
5.406 8.05
2.0 5.08
- -
9 9
More Options
16 AWG 16 AWG
12 12
26 26
0.059 0.15
20 0.51
50 1.27
0.509 1.29
97 144
175 260
5.406 8.05
2.0 5.08
- -
9 9
More Options
16 AWG 16 AWG
16 16
26 26
0.059 0.15
20 0.51
65 1.65
0.601 1.53
129 192
241 359
5.406 8.05
2.4 6.10
- -
9 9
More Options
16 AWG 16 AWG
19 19
26 26
0.059 0.15
20 0.51
65 1.65
0.630 1.60
154 229
315 469
5.406 8.05
2.5 6.35
- -
9 9
More Options
16 AWG 16 AWG
24 24
26 26
0.059 0.15
20 0.51
65 1.65
0.716 1.82
194 289
340 506
5.406 8.05
2.9 7.37
- -
8 8
More Options
16 AWG 16 AWG
30 30
26 26
0.059 0.15
20 0.51
85 2.16
0.811 2.06
243 362
439 653
5.406 8.05
3.2 8.13
- -
8 8
More Options
16 AWG 16 AWG
37 37
26 26
0.059 0.15
20 0.51
85 2.16
0.870 2.21
299 445
527 784
5.406 8.05
3.5 8.89
- -
7 7
More Options
14 AWG 14 AWG
3 3
41 41
0.073 0.19
20 0.51
50 1.27
0.342 0.87
38 57
77 115
3.391 5.05
1.4 3.56
20 20
25 25
More Options
14 AWG 14 AWG
4 4
41 41
0.073 0.19
20 0.51
50 1.27
0.375 0.95
51 76
97 144
3.391 5.05
1.5 3.81
16 16
20 20
More Options
14 AWG 14 AWG
6 6
41 41
0.073 0.19
20 0.51
50 1.27
0.445 1.13
76 113
134 199
3.391 5.05
1.8 4.57
16 16
20 20
More Options
14 AWG 14 AWG
8 8
41 41
0.073 0.19
20 0.51
50 1.27
0.495 1.26
102 152
175 260
3.391 5.05
1.9 4.83
14 14
17 17
More Options
14 AWG 14 AWG
9 9
41 41
0.073 0.19
20 0.51
50 1.27
0.516 1.31
115 171
189 281
3.391 5.05
2.1 5.33
14 14
17 17
More Options
14 AWG 14 AWG
10 10
41 41
0.073 0.19
20 0.51
65 1.65
0.601 1.53
127 189
226 336
3.391 5.05
2.4 6.10
10 10
12 12
More Options
14 AWG 14 AWG
12 12
41 41
0.073 0.19
20 0.51
65 1.65
0.608 1.54
153 228
258 384
3.391 5.05
2.5 6.35
10 10
12 12
More Options
14 AWG 14 AWG
16 16
41 41
0.073 0.19
20 0.51
65 1.65
0.666 1.69
204 304
332 494
3.391 5.05
2.7 6.86
10 10
12 12
More Options
14 AWG 14 AWG
18 18
41 41
0.073 0.19
20 0.51
65 1.65
0.697 1.77
230 342
419 624
3.391 5.05
2.8 7.11
10 10
12 12
More Options
14 AWG 14 AWG
25 25
41 41
0.073 0.19
20 0.51
65 1.65
0.806 2.05
318 473
488 726
3.391 5.05
3.2 8.13
9 9
11 11
More Options
12 AWG 12 AWG
3 3
65 65
0.094 0.24
20 0.51
50 1.27
0.389 0.99
60 89
108 161
2.137 3.18
1.6 4.06
25 25
30 30
More Options
12 AWG 12 AWG
4 4
65 65
0.094 0.24
20 0.51
50 1.27
0.420 1.07
81 121
137 204
2.137 3.18
1.7 4.32
20 20
24 24
More Options
12 AWG 12 AWG
5 5
65 65
0.094 0.24
20 0.51
50 1.27
0.462 1.17
101 150
165 246
2.137 3.18
1.9 4.83
20 20
24 24
More Options
12 AWG 12 AWG
6 6
65 65
0.094 0.24
20 0.51
50 1.27
0.502 1.28
142 211
194 289
2.137 3.18
2.0 5.08
20 20
24 24
More Options
12 AWG 12 AWG
7 7
65 65
0.094 0.24
20 0.51
50 1.27
0.502 1.28
141 210
219 326
2.137 3.18
2.0 5.08
17 17
21 21
More Options
12 AWG 12 AWG
12 12
65 65
0.094 0.24
20 0.51
65 1.65
0.687 1.74
243 362
425 632
2.137 3.18
2.8 7.11
12 12
15 15
More Options
10 AWG 10 AWG
3 3
105 105
0.117 0.30
25 0.64
50 1.27
0.462 1.17
97 144
160 238
1.339 1.99
2.0 5.08
35 35
40 40
More Options
10 AWG 10 AWG
4 4
105 105
0.117 0.30
25 0.64
50 1.27
0.502 1.28
129 192
202 301
1.339 1.99
2.0 5.08
28 28
32 32
More Options
10 AWG 10 AWG
5 5
105 105
0.117 0.30
25 0.64
50 1.27
0.579 1.47
161 240
257 382
1.339 1.99
2.0 5.08
28 28
32 32
More Options
10 AWG 10 AWG
7 7
105 105
0.117 0.30
25 0.64
60 1.52
0.628 1.60
226 336
337 502
1.339 1.99
2.4 6.10
24 24
28 28
More Options
10 AWG 10 AWG
12 12
105 105
0.117 0.30
25 0.64
80 2.03
0.867 2.20
389 579
671 999
1.339 1.99
3.5 8.89
18 18
20 20

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 13 Power-Limited Circuit Cables
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 AWM Style 2587
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2250 Instrumentation Tray Cable
  • UL 2277 Type WTTC
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Exceeds Ecolab PM-40-1 Material Resistance Test With 30-day Exposure, UL Verified V747862
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Black Thermoplastic Elastomer TPE: Other jacket colors available upon request

Resources

There are no downloadable resources for this product.