CU 600V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. CT Rated - Sunlight Resistant - For Direct Burial - VW-1 Rated - Silicone Free

Download Category Specifications
PDF Excel Table

Application

Southwire’s 600 or 1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. The jacket acts as gas/vapor-tight polymeric sheath that is extruded over the core per Sections 501.15(D) and 501.15(E) of the NEC, however when these cables are used in a hazardous location, they may need to be sealed further as described in more detail in the NEC. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated\ - Sunlight Resistant - For Direct Burial - Silicone Free.

Specifications

Select a set of products below for more information:
Cond. Size (AWG/Kcmil) Conductor Number Cond. Strands Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) DC Resistance @ 25C (ohms/1000') (ohms/km) AC Resistance @ 75C (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Raceway Ampacity @ 75C (amps) Raceway Ampacity @ 90C (amps)
More Options
14 14
2 2
7 7
30 0.76
45 1.14
0.355 0.90
25 37
66 98
2.631 3.92
3.170 4.72
1.4 3.56
20 20
25 25
More Options
14 14
3 3
7 7
30 0.76
45 1.14
0.376 0.96
38 57
90 134
2.631 3.92
3.170 4.72
1.5 3.81
20 20
25 25
More Options
14 14
4 4
7 7
30 0.76
45 1.14
0.409 1.04
51 76
109 162
2.631 3.92
3.170 4.72
1.6 4.06
16 16
20 20
More Options
14 14
5 5
7 7
30 0.76
45 1.14
0.447 1.14
64 95
129 192
2.631 3.92
3.170 4.72
1.8 4.57
16 16
20 20
More Options
14 14
6 6
7 7
30 0.76
45 1.14
0.486 1.23
76 113
151 225
2.631 3.92
3.170 4.72
1.9 4.83
16 16
20 20
More Options
14 14
7 7
7 7
30 0.76
45 1.14
0.482 1.22
89 132
168 250
2.631 3.92
3.170 4.72
1.9 4.83
14 14
17 17
More Options
14 14
8 8
7 7
30 0.76
60 1.52
0.559 1.42
102 152
208 310
2.631 3.92
3.170 4.72
2.2 5.59
14 14
17 17
More Options
14 14
9 9
7 7
30 0.76
60 1.52
0.598 1.52
114 170
231 344
2.631 3.92
3.170 4.72
2.4 6.10
14 14
17 17
More Options
14 14
12 12
7 7
30 0.76
60 1.52
0.670 1.70
153 228
295 439
2.631 3.92
3.170 4.72
2.7 6.86
10 10
12 12
More Options
14 14
15 15
7 7
30 0.76
60 1.52
0.742 1.88
191 284
358 533
2.631 3.92
3.170 4.72
3.0 7.62
10 10
12 12
More Options
14 14
19 19
7 7
30 0.76
60 1.52
0.780 1.98
242 360
439 653
2.631 3.92
3.170 4.72
3.1 7.87
10 10
12 12
More Options
14 14
25 25
7 7
30 0.76
80 2.03
0.952 2.42
319 475
602 896
2.631 3.92
3.170 4.72
3.8 9.65
9 9
11 11
More Options
14 14
30 30
7 7
30 0.76
80 2.03
1.006 2.56
386 574
707 1052
2.631 3.92
3.170 4.72
5.0 12.70
9 9
11 11
More Options
14 14
37 37
7 7
30 0.76
80 2.03
1.083 2.75
474 705
849 1263
2.631 3.92
3.170 4.72
5.4 13.72
8 8
10 10
More Options
12 12
2 2
7 7
30 0.76
45 1.14
0.388 0.99
40 60
88 131
1.662 2.47
2.002 2.98
1.6 4.06
25 25
30 30
More Options
12 12
3 3
7 7
30 0.76
45 1.14
0.408 1.04
61 91
117 174
1.662 2.47
2.002 2.98
1.6 4.06
25 25
30 30
More Options
12 12
4 4
7 7
30 0.76
45 1.14
0.449 1.14
81 121
152 226
1.662 2.47
2.002 2.98
1.8 4.57
20 20
24 24
More Options
12 12
5 5
7 7
30 0.76
45 1.14
0.487 1.24
101 150
174 259
1.662 2.47
2.002 2.98
1.9 4.83
20 20
24 24
More Options
12 12
7 7
7 7
30 0.76
60 1.52
0.561 1.42
142 211
248 369
1.662 2.47
2.002 2.98
2.2 5.59
17 17
21 21
More Options
12 12
9 9
7 7
30 0.76
60 1.52
0.657 1.67
182 271
315 469
1.662 2.47
2.002 2.98
2.6 6.60
17 17
21 21
More Options
12 12
10 10
7 7
30 0.76
60 1.52
0.714 1.81
202 301
349 519
1.662 2.47
2.002 2.98
2.9 7.37
12 12
15 15
More Options
12 12
12 12
7 7
30 0.76
60 1.52
0.738 1.87
243 362
404 601
1.662 2.47
2.002 2.98
3.0 7.62
12 12
15 15
More Options
12 12
15 15
7 7
30 0.76
60 1.52
0.819 2.08
303 451
496 738
1.662 2.47
2.002 2.98
3.3 8.38
12 12
15 15
More Options
12 12
19 19
7 7
30 0.76
80 2.03
0.904 2.30
385 573
647 963
1.662 2.47
2.002 2.98
3.6 9.14
12 12
15 15
More Options
12 12
25 25
7 7
30 0.76
80 2.03
1.051 2.67
511 760
835 1243
1.662 2.47
2.002 2.98
5.3 13.46
11 11
13 13
More Options
12 12
37 37
7 7
30 0.76
80 2.03
1.198 3.04
753 1121
1181 1758
1.662 2.47
2.002 2.98
6.0 15.24
10 10
12 12
More Options
10 10
2 2
7 7
30 0.76
45 1.14
0.448 1.14
64 95
121 180
1.040 1.55
1.253 1.86
1.8 4.57
35 35
40 40
More Options
10 10
3 3
7 7
30 0.76
45 1.14
0.472 1.20
97 144
166 247
1.040 1.55
1.253 1.86
1.9 4.83
35 35
40 40
More Options
10 10
4 4
7 7
30 0.76
45 1.14
0.547 1.39
129 192
229 341
1.040 1.55
1.253 1.86
2.2 5.59
28 28
32 32
More Options
10 10
5 5
7 7
30 0.76
60 1.52
0.603 1.53
161 240
273 406
1.040 1.55
1.253 1.86
2.4 6.10
28 28
32 32
More Options
10 10
7 7
7 7
30 0.76
60 1.52
0.657 1.67
226 336
361 537
1.040 1.55
1.253 1.86
2.6 6.60
24 24
28 28
More Options
10 10
8 8
7 7
30 0.76
60 1.52
0.711 1.81
257 382
408 607
1.040 1.55
1.253 1.86
2.8 7.11
24 24
28 28
More Options
10 10
9 9
7 7
30 0.76
60 1.52
0.765 1.94
289 430
455 677
1.040 1.55
1.253 1.86
3.1 7.87
24 24
28 28
More Options
10 10
12 12
7 7
30 0.76
80 2.03
0.904 2.30
386 574
625 930
1.040 1.55
1.253 1.86
3.6 9.14
17 17
20 20
More Options
10 10
15 15
7 7
30 0.76
80 2.03
1.001 2.54
483 719
764 1137
1.040 1.55
1.253 1.86
5.0 12.70
17 17
20 20
More Options
10 10
19 19
7 7
30 0.76
80 2.03
1.045 2.65
613 912
932 1387
1.040 1.55
1.253 1.86
5.2 13.21
17 17
20 20

* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: 7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes. VW-1 Rated
  3. Filler: Polypropylene filler on cables with 5 or less conductors
  4. Binder: Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket: Polyvinyl Chloride (PVC) Jacket