SPEC: 45258

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free SPEC45258

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Ground Size Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
4 4
7 7
0.142 0.36
45 1.14
1x10 1x10
60 1.52
0.755 1.92
238 354
404 601
More Options
6 AWG 6 AWG
4 4
7 7
0.178 0.45
45 1.14
1x8 1x8
80 2.03
0.902 2.29
379 564
613 912
More Options
4 AWG 4 AWG
4 4
7 7
0.225 0.57
45 1.14
1x8 1x8
80 2.03
0.938 2.38
572 851
812 1208
More Options
2 AWG 2 AWG
4 4
7 7
0.283 0.72
45 1.14
1x6 1x6
80 2.03
1.047 2.66
910 1354
1171 1743
More Options
1 AWG 1 AWG
4 4
19 19
0.322 0.82
55 1.40
1x6 1x6
80 2.03
1.229 3.12
1126 1676
1481 2204
More Options
1/0 AWG 1/0 AWG
4 4
19 19
0.362 0.92
55 1.40
1x6 1x6
80 2.03
1.328 3.37
1399 2082
1770 2634
More Options
2/0 AWG 2/0 AWG
4 4
19 19
0.405 1.03
55 1.40
1x6 1x6
80 2.03
1.43 3.63
1742 2592
2138 3182
More Options
3/0 AWG 3/0 AWG
4 4
19 19
0.456 1.16
55 1.40
1x4 1x4
80 2.03
1.55 3.94
2223 3308
2671 3975
More Options
4/0 AWG 4/0 AWG
4 4
19 19
0.512 1.30
55 1.40
1x4 1x4
110 2.79
1.717 4.36
2770 4122
3367 5011
More Options
250 KCMIL 250 KCMIL
4 4
37 37
0.558 1.42
65 1.65
1x4 1x4
110 2.79
1.866 4.74
3249 4835
3935 5856
More Options
350 KCMIL 350 KCMIL
4 4
37 37
0.661 1.68
65 1.65
1x3 1x3
110 2.79
2.105 5.35
4530 6741
5314 7908
More Options
500 KCMIL 500 KCMIL
4 4
37 37
0.789 2.00
65 1.65
1x2 1x2
110 2.79
2.407 6.11
6444 9590
7324 10899
More Options
600 KCMIL 600 KCMIL
4 4
61 61
0.865 2.20
80 2.03
140 3.56
2.867 7.28
8144 12120
9634 14337
More Options
750 KCMIL 750 KCMIL
4 4
61 61
0.968 2.46
80 2.03
140 3.56
3.032 7.70
9616 14310
11355 16898

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
4 4
3 7.62
528 239.50
0.653 0.97
0.810 1.21
0.052 0.08
40 40
44 44
More Options
6 AWG 6 AWG
4 4
3.6 9.14
839 380.56
0.411 0.61
0.510 0.76
0.051 0.08
52 52
60 60
More Options
4 AWG 4 AWG
4 4
3.8 9.65
1335 605.55
0.258 0.38
0.320 0.48
0.048 0.07
68 68
76 76
More Options
2 AWG 2 AWG
4 4
5.2 13.21
2123 962.98
0.162 0.24
0.201 0.30
0.045 0.07
92 92
104 104
More Options
1 AWG 1 AWG
4 4
6.1 15.49
2678 1214.72
0.128 0.19
0.159 0.24
0.046 0.07
104 104
116 116
More Options
1/0 AWG 1/0 AWG
4 4
6.6 16.76
3379 1532.69
0.102 0.15
0.127 0.19
0.044 0.07
120 120
136 136
More Options
2/0 AWG 2/0 AWG
4 4
7.2 18.29
4259 1931.85
0.082 0.12
0.102 0.15
0.043 0.06
140 140
156 156
More Options
3/0 AWG 3/0 AWG
4 4
7.8 19.81
5369 2435.34
0.064 0.10
0.079 0.12
0.042 0.06
160 160
180 180
More Options
4/0 AWG 4/0 AWG
4 4
8.6 21.84
6771 3071.27
0.051 0.08
0.063 0.09
0.041 0.06
184 184
208 208
More Options
250 KCMIL 250 KCMIL
4 4
9.3 23.62
8000 3628.74
0.043 0.06
0.053 0.08
0.041 0.06
204 204
232 232
More Options
350 KCMIL 350 KCMIL
4 4
12.6 32.00
11200 5080.23
0.031 0.05
0.039 0.06
0.040 0.06
248 248
280 280
More Options
500 KCMIL 500 KCMIL
4 4
14.4 36.58
16000 7257.47
0.021 0.03
0.027 0.04
0.039 0.06
304 304
344 344
More Options
600 KCMIL 600 KCMIL
4 4
17.2 43.69
15360 6967.17
0.018 0.03
0.025 0.04
0.039 0.06
336 336
380 380
More Options
750 KCMIL 750 KCMIL
4 4
18.2 46.23
19200 8708.97
0.014 0.02
0.022 0.03
0.038 0.06
380 380
428 428

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

Construction

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Resources

There are no downloadable resources for this product.