SPEC: 45258

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
4 4
7 7
0.141 0.36
45 1.14
60 1.52
0.755 1.92
238 354
403 600
More Options
6 AWG 6 AWG
4 4
7 7
0.177 0.45
45 1.14
60 1.52
0.902 2.29
378 563
613 912
More Options
4 AWG 4 AWG
4 4
7 7
0.225 0.57
45 1.14
80 2.03
0.918 2.33
572 851
804 1196
More Options
2 AWG 2 AWG
4 4
7 7
0.282 0.72
45 1.14
80 2.03
1.046 2.66
909 1353
1185 1763
More Options
1 AWG 1 AWG
4 4
19 19
0.322 0.82
55 1.40
80 2.03
1.202 3.05
1125 1674
1496 2226
More Options
1/0 AWG 1/0 AWG
4 4
19 19
0.361 0.92
55 1.40
80 2.03
1.299 3.30
1399 2082
1754 2610
More Options
2/0 AWG 2/0 AWG
4 4
19 19
0.405 1.03
55 1.40
80 2.03
1.420 3.61
1742 2592
2144 3191
More Options
3/0 AWG 3/0 AWG
4 4
19 19
0.456 1.16
55 1.40
80 2.03
1.521 3.86
2223 3308
2693 4008
More Options
4/0 AWG 4/0 AWG
4 4
19 19
0.512 1.30
55 1.40
110 2.79
1.721 4.37
2769 4121
3425 5097
More Options
250 KCMIL 250 KCMIL
4 4
37 37
0.558 1.42
65 1.65
110 2.79
1.842 4.68
3248 4834
4003 5957
More Options
350 KCMIL 350 KCMIL
4 4
37 37
0.661 1.68
65 1.65
110 2.79
2.095 5.32
4530 6741
5351 7963
More Options
500 KCMIL 500 KCMIL
4 4
37 37
0.789 2.00
65 1.65
110 2.79
2.382 6.05
6443 9588
7427 11053
More Options
600 KCMIL 600 KCMIL
4 4
61 61
0.865 2.20
80 2.03
140 3.56
2.867 7.28
8144 12120
9633 14335
More Options
750 KCMIL 750 KCMIL
4 4
61 61
0.968 2.46
80 2.03
140 3.56
2.962 7.52
9616 14310
11320 16846
Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
8 AWG 8 AWG
4 4
3.0 7.62
422 191.42
0.653 0.97
0.786 1.17
0.052 0.08
40 40
44 44
More Options
6 AWG 6 AWG
4 4
3.6 9.14
671 304.36
0.411 0.61
0.495 0.74
0.051 0.08
52 52
60 60
More Options
4 AWG 4 AWG
4 4
3.7 9.40
1068 484.44
0.258 0.38
0.310 0.46
0.048 0.07
68 68
76 76
More Options
2 AWG 2 AWG
4 4
5.2 13.21
1698 770.20
0.162 0.24
0.195 0.29
0.045 0.07
92 92
104 104
More Options
1 AWG 1 AWG
4 4
6.0 15.24
2142 971.59
0.128 0.19
0.154 0.23
0.046 0.07
104 104
116 116
More Options
1/0 AWG 1/0 AWG
4 4
6.5 16.51
2703 1226.06
0.102 0.15
0.122 0.18
0.044 0.07
120 120
136 136
More Options
2/0 AWG 2/0 AWG
4 4
7.1 18.03
3407 1545.39
0.081 0.12
0.097 0.14
0.043 0.06
140 140
156 156
More Options
3/0 AWG 3/0 AWG
4 4
7.6 19.30
4295 1948.18
0.064 0.10
0.078 0.12
0.042 0.06
160 160
180 180
More Options
4/0 AWG 4/0 AWG
4 4
8.6 21.84
5416 2456.65
0.051 0.08
0.062 0.09
0.041 0.06
184 184
208 208
More Options
250 KCMIL 250 KCMIL
4 4
9.2 23.37
6400 2902.99
0.043 0.06
0.053 0.08
0.041 0.06
204 204
232 232
More Options
350 KCMIL 350 KCMIL
4 4
12.6 32.00
8960 4064.18
0.031 0.05
0.039 0.06
0.040 0.06
248 248
280 280
More Options
500 KCMIL 500 KCMIL
4 4
14.3 36.32
12800 5805.98
0.022 0.03
0.029 0.04
0.039 0.06
304 304
344 344
More Options
600 KCMIL 600 KCMIL
4 4
17.2 43.69
15360 6967.17
0.018 0.03
0.025 0.04
0.039 0.06
336 336
380 380
More Options
750 KCMIL 750 KCMIL
4 4
17.8 45.21
19200 8708.97
0.014 0.02
0.022 0.03
0.038 0.06
380 380
428 428

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation: Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler: Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder: Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket: Polyvinyl Chloride (PVC) Jacket

Resources

There are no downloadable resources for this product.