Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
8 AWG
8 AWG
|
4
4
|
7
7
|
0.141
0.36
|
45
1.14
|
60
1.52
|
0.755
1.92
|
238
354
|
403
600
|
| More Options |
6 AWG
6 AWG
|
4
4
|
7
7
|
0.177
0.45
|
45
1.14
|
80
2.03
|
0.902
2.29
|
378
563
|
613
912
|
| More Options |
4 AWG
4 AWG
|
4
4
|
7
7
|
0.225
0.57
|
45
1.14
|
80
2.03
|
0.938
2.38
|
572
851
|
812
1208
|
| More Options |
2 AWG
2 AWG
|
4
4
|
7
7
|
0.282
0.72
|
45
1.14
|
80
2.03
|
1.047
2.66
|
909
1353
|
1189
1769
|
| More Options |
1 AWG
1 AWG
|
4
4
|
19
19
|
0.322
0.82
|
55
1.40
|
80
2.03
|
1.215
3.09
|
1125
1674
|
1504
2238
|
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
19
19
|
0.361
0.92
|
55
1.40
|
80
2.03
|
1.328
3.37
|
1399
2082
|
1774
2640
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
19
19
|
0.405
1.03
|
55
1.40
|
80
2.03
|
1.430
3.63
|
1742
2592
|
2155
3207
|
| More Options |
3/0 AWG
3/0 AWG
|
4
4
|
19
19
|
0.456
1.16
|
55
1.40
|
80
2.03
|
1.551
3.94
|
2223
3308
|
2716
4042
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
19
19
|
0.512
1.30
|
55
1.40
|
110
2.79
|
1.751
4.45
|
2769
4121
|
3447
5130
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
37
37
|
0.558
1.42
|
65
1.65
|
110
2.79
|
1.866
4.74
|
3249
4835
|
4025
5990
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
37
37
|
0.661
1.68
|
65
1.65
|
110
2.79
|
2.105
5.35
|
4530
6741
|
5314
7908
|
| More Options |
500 KCMIL
500 KCMIL
|
4
4
|
37
37
|
0.789
2.00
|
65
1.65
|
110
2.79
|
2.407
6.11
|
6444
9590
|
7455
11094
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
61
61
|
0.865
2.20
|
80
2.03
|
140
3.56
|
2.867
7.28
|
8144
12120
|
9634
14337
|
| More Options |
750 KCMIL
750 KCMIL
|
4
4
|
61
61
|
0.968
2.46
|
80
2.03
|
140
3.56
|
3.032
7.70
|
9616
14310
|
11355
16898
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
8 AWG
8 AWG
|
4
4
|
3.0
7.62
|
422
191.42
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
40
40
|
44
44
|
| More Options |
6 AWG
6 AWG
|
4
4
|
3.6
9.14
|
671
304.36
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
52
52
|
60
60
|
| More Options |
4 AWG
4 AWG
|
4
4
|
3.8
9.65
|
1068
484.44
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
68
68
|
76
76
|
| More Options |
2 AWG
2 AWG
|
4
4
|
5.2
13.21
|
1698
770.20
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
92
92
|
104
104
|
| More Options |
1 AWG
1 AWG
|
4
4
|
6.1
15.49
|
2142
971.59
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
104
104
|
116
116
|
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
6.6
16.76
|
2703
1226.06
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
120
120
|
136
136
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
2
5.08
|
3407
1545.39
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
140
140
|
156
156
|
| More Options |
3/0 AWG
3/0 AWG
|
4
4
|
7.8
19.81
|
4295
1948.18
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
160
160
|
180
180
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
8.7
22.10
|
5416
2456.65
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
184
184
|
208
208
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
9.3
23.62
|
6400
2902.99
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
204
204
|
232
232
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
12.6
32.00
|
8960
4064.18
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
248
248
|
280
280
|
| More Options |
500 KCMIL
500 KCMIL
|
4
4
|
14.4
36.58
|
12800
5805.98
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
304
304
|
344
344
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
17.2
43.69
|
15360
6967.17
|
0.018
0.03
|
0.025
0.04
|
0.039
0.06
|
336
336
|
380
380
|
| More Options |
750 KCMIL
750 KCMIL
|
4
4
|
18.2
46.23
|
19200
8708.97
|
0.014
0.02
|
0.022
0.03
|
0.038
0.06
|
380
380
|
428
428
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.