Southwire’s 600 or 1000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. CT Rated 1/0 and Larger - Sunlight Resistant - Silicone Free. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
19
19
|
0.361
0.92
|
55
1.40
|
50
1.27
|
0.590
1.50
|
325
484
|
431
641
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
19
19
|
0.405
1.03
|
55
1.40
|
50
1.27
|
0.634
1.61
|
410
610
|
526
783
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
0.498
1.26
|
55
1.40
|
50
1.27
|
0.726
1.84
|
653
972
|
790
1176
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
37
37
|
0.542
1.38
|
65
1.65
|
60
1.52
|
0.836
2.12
|
771
1147
|
970
1444
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
37
37
|
0.661
1.68
|
65
1.65
|
75
1.91
|
0.935
2.37
|
1080
1607
|
1307
1945
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
37
37
|
0.789
2.00
|
65
1.65
|
75
1.91
|
1.060
2.69
|
1543
2296
|
1807
2689
|
| More Options |
750 KCMIL
750 KCMIL
|
1
1
|
61
61
|
0.968
2.46
|
80
2.03
|
75
1.91
|
1.294
3.29
|
2315
3445
|
2674
3979
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
2.3
5.84
|
844
382.83
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.5
6.35
|
1064
482.62
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
2.9
7.37
|
1692
767.48
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
230
230
|
260
260
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
3.2
8.13
|
2000
907.18
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
255
255
|
290
290
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
3.7
9.40
|
2800
1270.06
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
310
310
|
350
350
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
5.3
13.46
|
4000
1814.37
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
380
380
|
430
430
|
| More Options |
750 KCMIL
750 KCMIL
|
1
1
|
6.5
16.51
|
6000
2721.55
|
0.014
0.02
|
0.022
0.03
|
0.038
0.06
|
475
475
|
535
535
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.