Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
14 AWG
14 AWG
|
1
1
|
19
19
|
0.073
0.19
|
75
1.91
|
|
0.224
0.57
|
12
18
|
29
43
|
| More Options |
12 AWG
12 AWG
|
1
1
|
19
19
|
0.088
0.22
|
75
1.91
|
|
0.243
0.62
|
20
30
|
39
58
|
| More Options |
10 AWG
10 AWG
|
1
1
|
19
19
|
0.113
0.29
|
75
1.91
|
75
1.91
|
0.263
0.67
|
32
48
|
53
79
|
| More Options |
8 AWG
8 AWG
|
1
1
|
19
19
|
0.141
0.36
|
85
2.16
|
|
0.313
0.80
|
50
74
|
79
118
|
| More Options |
8 AWG
8 AWG
|
1
1
|
19
19
|
0.141
0.36
|
85
2.16
|
|
0.313
0.80
|
50
74
|
79
118
|
| More Options |
6 AWG
6 AWG
|
1
1
|
19
19
|
0.177
0.45
|
85
2.16
|
85
2.16
|
0.349
0.89
|
81
121
|
114
170
|
| More Options |
4 AWG
4 AWG
|
1
1
|
19
19
|
0.225
0.57
|
85
2.16
|
|
0.396
1.01
|
128
190
|
168
250
|
| More Options |
2 AWG
2 AWG
|
1
1
|
19
19
|
0.286
0.73
|
85
2.16
|
85
2.16
|
0.456
1.16
|
204
304
|
250
372
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
19
19
|
0.361
0.92
|
105
2.67
|
|
0.570
1.45
|
326
485
|
396
589
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
19
19
|
0.405
1.03
|
105
2.67
|
|
0.614
1.56
|
410
610
|
488
726
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
19
19
|
0.456
1.16
|
105
2.67
|
105
2.67
|
0.664
1.69
|
518
771
|
604
899
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
0.512
1.30
|
105
2.67
|
|
0.720
1.83
|
655
975
|
750
1116
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
37
37
|
0.558
1.42
|
120
3.05
|
120
3.05
|
0.782
1.99
|
771
1147
|
879
1308
|
| More Options |
300 KCMIL
300 KCMIL
|
1
1
|
37
37
|
0.610
1.55
|
120
3.05
|
120
3.05
|
0.851
2.16
|
926
1378
|
1051
1564
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
37
37
|
0.661
1.68
|
120
3.05
|
|
0.901
2.29
|
1080
1607
|
1215
1808
|
| More Options |
400 KCMIL
400 KCMIL
|
1
1
|
37
37
|
0.706
1.79
|
120
3.05
|
|
0.946
2.40
|
1235
1838
|
1378
2051
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
37
37
|
0.789
2.00
|
120
3.05
|
|
1.006
2.56
|
1543
2296
|
1685
2508
|
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
61
61
|
0.865
2.20
|
135
3.43
|
|
1.136
2.89
|
1852
2756
|
2042
3039
|
| More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
61
61
|
1.117
2.84
|
135
3.43
|
|
1.387
3.52
|
3088
4595
|
3325
4948
|
*VW-1 Rated
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
14 AWG
14 AWG
|
1
1
|
0.9
2.29
|
|
2.631
3.92
|
3.170
4.72
|
0.058
0.09
|
20
20
|
25
25
|
| More Options |
12 AWG
12 AWG
|
1
1
|
1.0
2.54
|
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
25
25
|
30
30
|
| More Options |
10 AWG
10 AWG
|
1
1
|
1.1
2.79
|
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
35
35
|
40
40
|
| More Options |
8 AWG
8 AWG
|
1
1
|
1.3
3.30
|
132
59.87
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
8 AWG
8 AWG
|
1
1
|
1.3
3.30
|
132
59.87
|
0.653
0.97
|
0.786
1.17
|
0.052
0.08
|
50
50
|
55
55
|
| More Options |
6 AWG
6 AWG
|
1
1
|
1.4
3.56
|
209
94.80
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
1
1
|
1.6
4.06
|
333
151.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
| More Options |
2 AWG
2 AWG
|
1
1
|
1.8
4.57
|
530
240.40
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
115
115
|
130
130
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
2.3
5.84
|
844
382.83
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.5
6.35
|
1064
482.62
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.7
6.86
|
1342
608.72
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
2.9
7.37
|
1692
767.48
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
230
230
|
260
260
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
3.1
7.87
|
2000
907.18
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
255
255
|
290
290
|
| More Options |
300 KCMIL
300 KCMIL
|
1
1
|
3.4
8.64
|
2400
1088.62
|
0.036
0.05
|
0.045
0.07
|
0.041
0.06
|
285
285
|
320
320
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
3.6
9.14
|
2800
1270.06
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
310
310
|
350
350
|
| More Options |
400 KCMIL
400 KCMIL
|
1
1
|
3.8
9.65
|
3200
1451.49
|
0.027
0.04
|
0.035
0.05
|
0.028
0.04
|
335
335
|
380
380
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
5.0
12.70
|
4000
1814.37
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
380
380
|
430
430
|
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
5.7
14.48
|
4800
2177.24
|
0.018
0.03
|
0.025
0.04
|
0.039
0.06
|
420
420
|
475
475
|
| More Options |
1000 KCMIL
1000 KCMIL
|
1
1
|
6.9
17.53
|
8000
3628.74
|
0.011
0.02
|
0.018
0.03
|
0.037
0.06
|
545
545
|
615
615
|
Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.
| Size | Black | White | Red | Green | Green/Yellow |
|
AWG/Kcmil
AWG/Kcmil
|
|
|
|
|
|
|
14
14
|
|
|
|
|
|
|
12
12
|
596376
596376
|
596377
596377
|
|
|
|
|
10
10
|
583665
583665
|
583687
583687
|
|
|
|
|
2
2
|
|
|
|
|
|
|
1/0
1/0
|
|
|
|
677562
677562
|
|
|
2/0
2/0
|
|
|
|
|
|
|
3/0
3/0
|
|
|
|
|
|
|
4/0
4/0
|
|
|
|
|
|
|
250
250
|
|
|
|
|
|
|
300
300
|
599400
599400
|
599401
599401
|
|
|
|
|
350
350
|
|
|
|
|
|
|
400
400
|
|
|
|
|
|
|
500
500
|
|
|
|
|
|
|
600
600
|
|
|
|
|
|
|
1000
1000
|
|
|
|
|