Duraclad® Type MC MC56

14/2 AWG Copper THHN/THWN Insulated Singles. Green Copper THHN Insulated Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Steel Interlocked Armor. Also available in Blue Steel Armor.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Duraclad® Type MC Cable is suitable for use as follows:

  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22(C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

Specifications

Select a set of products below for more information:
Conductor Ground Wire Neutral Wire
Size (AWG or kcmil) (mm2) No. of Conductors Stranding Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Size (AWG) Ground Size UOM Size (AWG) Conductor Colors
More Options
12 AWG 12 AWG
2 2
Solid Solid
484 12.29
206 307
12 12
AWG AWG
12 12
RED/WHT/GRN RED/WHT/GRN
More Options
12 AWG 12 AWG
2 2
Stranded Stranded
530 13.46
174 258
12 12
AWG AWG
BLK, WHT, GRN BLK, WHT, GRN
More Options
12 AWG 12 AWG
2 2
Stranded Stranded
504 12.82
158 235
12 12
AWG AWG
12 12
BLK, WHT, GRN BLK, WHT, GRN
More Options
12 AWG 12 AWG
3 3
Solid Solid
514 13.07
181 269
12 12
AWG AWG
12 12
GRY, BRN, ORG, GRN GRY, BRN, ORG, GRN
More Options
12 AWG 12 AWG
3 3
Stranded Stranded
585 14.86
208 309
12 12
AWG AWG
BLK, RED, WHT, GRN BLK, RED, WHT, GRN
More Options
12 AWG 12 AWG
3 3
Stranded Stranded
538 13.68
191 284
12 12
AWG AWG
12 12
BLK, WHT, RED, GRN BLK, WHT, RED, GRN
More Options
12 AWG 12 AWG
4 4
Solid Solid
550 13.97
278 413
12 12
AWG AWG
12 12
BLK/WHT/RED/WHT-RED/GRN BLK/WHT/RED/WHT-RED/GRN
More Options
12 AWG 12 AWG
4 4
Stranded Stranded
585 14.86
297 443
12 12
AWG AWG
12 12
BLK/RED/BLU/WHT/GRN BLK/RED/BLU/WHT/GRN
More Options
10 AWG 10 AWG
2 2
Solid Solid
550 13.98
205 305
10 10
AWG AWG
10 10
RED, WHT, GRN RED, WHT, GRN
More Options
10 AWG 10 AWG
2 2
Stranded Stranded
583 14.82
222 330
10 10
AWG AWG
10 10
BLK, WHT, GRN BLK, WHT, GRN
More Options
10 AWG 10 AWG
4 4
Solid Solid
633 16.09
297 441
10 10
AWG AWG
10 10
BLK, WHT, RED, BLU, GRN BLK, WHT, RED, BLU, GRN

Standards & References

Southwire Duraclad® Type MC Cable meets or exceeds the following requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A-59544
  • NFPA 70 (National Electrical Code), Article 330
  • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202" (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Firestop Systems
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire Duraclad Type MC Cable is constructed with soft-drawn copper, Type THHN/THWN conductors and a green insulated grounding conductor. The conductors are cabled together and a binder tape bearing the print legend is wrapped on the assembly. Light weight galvanized steel interlocked armor is applied over the assembly. Blue steel armor is also available.

Resources

There are no downloadable resources for this product.