Southwire Armorlite® Type MC Riser Feeder cable is suitable for use as follows:
- Riser cable, vertical applications
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Conductors are Type THHN/THWN-2 rated 90ºC Wet and Dry. Unjacketed MC cables are not rated for wet locations.
Southwire Armorlite® Type MC Riser Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
| Cond. Size | Conductor Number | Color | Diameter Over Conductor (in) (cm) | Cond. Strands | Insulation Thickness (mils) (mm) | Ground Size | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
1 AWG
1 AWG
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.322
0.82
|
19
19
|
60
1.52
|
1x6 GG
1x6 GG
|
1.658
4.21
|
|
|
1782
2652
|
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
BK,RD,BE,WE
BK,RD,BE,WE
|
0.360
0.91
|
19
19
|
60
1.52
|
1x6 GG
1x6 GG
|
1.748
4.44
|
|
|
2103
3130
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.364
0.92
|
19
19
|
60
1.52
|
1x3
1x3
|
1.924
4.89
|
50
1.27
|
1.924
4.89
|
2664
3964
|
| More Options |
3/0 AWG
3/0 AWG
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.409
1.04
|
19
19
|
60
1.52
|
1x2
1x2
|
2.086
5.30
|
60
1.52
|
2.086
5.30
|
3234
4813
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.46
1.17
|
19
19
|
60
1.52
|
1x2
1x2
|
2.113
5.37
|
60
1.52
|
2.113
5.37
|
3791
5642
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.641
1.63
|
37
37
|
70
1.78
|
1x1 GG
1x1 GG
|
2.518
6.40
|
|
|
5781
8603
|
| More Options |
400 KCMIL
400 KCMIL
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.659
1.67
|
37
37
|
70
1.78
|
1x4/0
1x4/0
|
2.841
7.22
|
50
1.27
|
2.841
7.22
|
7003
10422
|
Note: Conductor number = number of phase conductors. Does not include ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
1 AWG
1 AWG
|
4
4
|
11.6
29.46
|
2142
971.59
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
104
104
|
116
116
|
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
12.2
30.99
|
2703
1226.06
|
0.102
0.15
|
0.133
0.20
|
0.044
0.07
|
120
120
|
136
136
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
13.4
34.04
|
3407
1545.39
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
140
140
|
156
156
|
| More Options |
3/0 AWG
3/0 AWG
|
4
4
|
14.6
37.08
|
4295
1948.18
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
160
160
|
180
180
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
14.7
37.34
|
5416
2456.65
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
184
184
|
208
208
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
17.6
44.70
|
8960
4064.18
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
248
248
|
280
280
|
| More Options |
400 KCMIL
400 KCMIL
|
4
4
|
19.8
50.29
|
12800
5805.98
|
0.044
0.07
|
0.054
0.08
|
0.040
0.06
|
268
268
|
304
304
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.