Southwire Armorlite® Type MC Feeder Cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for Wet Location per NEC 330.10(A)(11)
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
| Cond. Size | Conductor Number | Color | Diameter Over Conductor (in) (cm) | Cond. Strands | Insulation Thickness (mils) (mm) | Ground Size | Diameter Over Armor (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
BK,RD,BE,WE,GN,GN/YW
BK,RD,BE,WE,GN,GN/YW
|
0.361
0.92
|
19
19
|
60
1.52
|
2x3
2x3
|
1.677
4.26
|
2377
3537
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
1-BK,2-RD,3-BE,WE,GN
1-BK,2-RD,3-BE,WE,GN
|
0.395
1.00
|
19
19
|
60
1.52
|
1x6
1x6
|
1.578
4.01
|
2250
3348
|
| More Options |
4/0 AWG
4/0 AWG
|
5
5
|
BK,RD,BE,WE,WE/BK,GN
BK,RD,BE,WE,WE/BK,GN
|
0.512
1.30
|
19
19
|
60
1.52
|
1x4
1x4
|
1.961
4.98
|
4126
6140
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
BK,RD,BE,WE
BK,RD,BE,WE
|
0.558
1.42
|
37
37
|
70
1.78
|
1x2
1x2
|
1.954
4.96
|
3994
5944
|
| More Options |
250 KCMIL
250 KCMIL
|
5
5
|
BK,RD,BE,WE,WE,GN
BK,RD,BE,WE,WE,GN
|
0.558
1.42
|
37
37
|
70
1.78
|
1x4
1x4
|
2.136
5.43
|
4798
7140
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
BK,BK,RD,RD,GN
BK,BK,RD,RD,GN
|
0.661
1.68
|
37
37
|
70
1.78
|
1x2/0
1x2/0
|
2.324
5.90
|
5673
8442
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
BK,RD,BE,WE,GN
BK,RD,BE,WE,GN
|
0.865
2.20
|
61
61
|
80
2.03
|
1x2
1x2
|
2.716
6.90
|
8702
12950
|
Note: Conductor number = number of phase conductors. Does not include green ground.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
11.7
29.72
|
2703
1226.06
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
120
120
|
136
136
|
| More Options |
2/0 AWG
2/0 AWG
|
4
4
|
11.0
27.94
|
4259
1931.85
|
0.081
0.12
|
0.101
0.15
|
0.043
0.06
|
140
140
|
156
156
|
| More Options |
4/0 AWG
4/0 AWG
|
5
5
|
13.7
34.80
|
6771
3071.27
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
184
184
|
182
182
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
13.7
34.80
|
6400
2902.99
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
204
204
|
232
232
|
| More Options |
250 KCMIL
250 KCMIL
|
5
5
|
15
38.10
|
8000
3628.74
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
204
204
|
203
203
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
16.3
41.40
|
11200
5080.23
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
248
248
|
280
280
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
19
48.26
|
19200
8708.97
|
0.018
0.03
|
0.025
0.04
|
0.039
0.06
|
336
336
|
380
380
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.