Armorlite Riser MC™ Cable CU Feeder THHN/THWN-2 Conductors

4/0-4 AWG Copper THHN Insulated Singles. Bare Copper Grounding Conductor. UL Listed. 600 Volts. Binder Jacket for Continuous Conductor Support. Lightweight Aluminum Interlocked Armor.

Download Category Specifications
PDF Excel Table

Application

Suitable for use as follows:

  • Riser Cable, vertical applications
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multiresidential buildings.
  • Concealed or exposed installations.
  • Power, lighting, control, and signal circuits
  • Fished or embedded in plaster
  • Installation in cable tray and approved raceways.
  • Concealed or exposed installations
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5
  • Installation in cable tray and approved raceways
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
583932
4 4
4 AWG 4 AWG
1 1
40 1.02
8 8
1326 33.70
1008 1500
646552
5 5
3 AWG 3 AWG
1 1
50 1.27
1924 48.88
2627 3909
646808
4 4
2/0 AWG 2/0 AWG
1 1
50 1.27
3 3
1863 47.32
2579 3838
587704
0 0
3/0 AWG 3/0 AWG
19 19
50 1.27
0 0
1944 49.38
2647 3940
678001
4 4
3/0 AWG 3/0 AWG
1 1
50 1.27
4 4
2101 53.38
3081 4585
587710
4 4
4/0 AWG 4/0 AWG
1 1
50 1.27
0 0
2318 58.88
4237 6305
583433
4 4
4/0 AWG 4/0 AWG
1 1
50 1.27
4 4
2220 56.40
3714 5526
677978
4 4
250 KCMIL 250 KCMIL
1 1
60 1.52
1/0 1/0
2268 57.61
4416 6572
674326
4 4
350 KCMIL 350 KCMIL
1 1
60 1.52
1 1
2518 63.96
5782 8604
679715
4 4
400 KCMIL 400 KCMIL
1 1
60 1.52
4/0 4/0
2743 69.67
6963 10363
586733
4 4
600 KCMIL 600 KCMIL
1 1
70 1.78
2 2
3039 77.21
9194 13683
598079
3 3
750 KCMIL 750 KCMIL
1 1
70 1.78
1/0 1/0
2890 73.41
3637 5413
587705
4 4
1 AWG 1 AWG
1 1
50 1.27
0 0
1818 46.18
1933 2876

Standards & References

Southwire's Armorlite® Type MC Cable - Multi-Circuit meets or exceeds the following requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202" (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire Copper Riser MC™ is constructed with Type THHN/THWN-2 conductors and a bare equipment grounding conductor. A binder tape is wrapped over the conductors and an integral polymeric binder jacket is applied under armor for continuous conductor support. Aluminum interlocking armor is applied snuggly over the assembly. An optional overall PVC Jacket can be applied over the armor.

Resources

There are no downloadable resources for this product.