Armorlite Riser MC™ Cable CU Feeder THHN/THWN-2 Conductors MC37

4/0-4 AWG Copper THHN Insulated Singles. Bare Copper Grounding Conductor. UL Listed. 600 Volts. Binder Jacket for Continuous Conductor Support. Lightweight Aluminum Interlocked Armor.

Download Category Specifications
PDF Excel Table

Application & Features

Suitable for use as follows:

  • Riser Cable, vertical applications
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multiresidential buildings.
  • Concealed or exposed installations.
  • Power, lighting, control, and signal circuits
  • Fished or embedded in plaster
  • Installation in cable tray and approved raceways.
  • Concealed or exposed installations
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5
  • Installation in cable tray and approved raceways
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).

Specifications

Select a set of products below for more information:
Conductor Ground Wire
Size (AWG or kcmil) (mm2) No. of Conductors Stranding Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Size (AWG) Ground Size UOM Conductor Colors
More Options
2/0 AWG 2/0 AWG
4 4
Solid Solid
1924 48.88
2665 3966
3 3
AWG AWG
BROWN/ORANGE/YELLOW/GRAY/#3 GREEN GROUND BROWN/ORANGE/YELLOW/GRAY/#3 GREEN GROUND
More Options
3/0 AWG 3/0 AWG
4 4
Solid Solid
2086 52.98
3234 4813
2 2
AWG AWG
BROWN/ORANGE/YELLOW/GRAY/#2 GREEN GROUND BROWN/ORANGE/YELLOW/GRAY/#2 GREEN GROUND
More Options
4/0 AWG 4/0 AWG
4 4
Solid Solid
2113 53.67
3791 5642
2 2
AWG AWG
BROWN/ORANGE/YELLOW/GRAY/#2 GREEN GROUND BROWN/ORANGE/YELLOW/GRAY/#2 GREEN GROUND
More Options
400 KCMIL 400 KCMIL
4 4
Solid Solid
2841 72.17
7003 10422
4/0 4/0
AWG AWG
BROWN/ORANGE/YELLOW/GRAY/#4/0GREEN GROUND BROWN/ORANGE/YELLOW/GRAY/#4/0GREEN GROUND

Standards & References

Southwire's Armorlite® Type MC Cable - Multi-Circuit meets or exceeds the following requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202" (70,000 Btu/hr) Vertical Cable Tray Flame Test
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire Copper Riser MC™ is constructed with Type THHN/THWN-2 conductors and a bare equipment grounding conductor. A binder tape is wrapped over the conductors and an integral polymeric binder jacket is applied under armor for continuous conductor support. Aluminum interlocking armor is applied snuggly over the assembly. An optional overall PVC Jacket can be applied over the armor.

Resources