Alumaflex™ Type MC AL Feeder THHN/THWN-2 Conductors with PVC Jacket

Alumaflex™ Type MC AL Feeder THHN/THWN-2 Conductors with PVC Jacket

900/4 kcmil AlumaFlex™ THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor. Overall PVC Jacket.
Download Category Specifications:
PDF Excel Table

Application

Type MC Cable - "flame retardant sunlight resistant PVC Jacket" is suitable for use as follows:

  • Suitable for Wet Location per NEC 330.10(11)
  • Direct burial applications, installation in concrete and where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloricacids
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multiresidential buildings
  • Power, lighting, control, and signal circuits.
  • Fished or embedded in plaster
  • Concealed or exposed installations.
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • As aerial cable on a messenger
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables perNEC 645.5(D) & 645.5(D)(2).
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.

Specifications

measurement
imperial metric
Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
677987 2 2 4/0 AWG 4/0 AWG 19 19 2/0 2/0 1496 38.00 937 1394
641160 3 3 4/0 AWG 4/0 AWG 19 19 50 1.27 2 2 1722 43.74 1289 1918
677813 4 4 4/0 AWG 4/0 AWG 19 19 50 1.27 2 2 1965 49.91 1648 2453
599377 3 3 250 KCMIL 250 KCMIL 22 22 60 1.52 1/0 1/0 1945 49.42 1599 2380
679730 4 4 250 KCMIL 250 KCMIL 22 22 60 1.52 2 2 2033 51.65 1855 2760
640788 4 4 350 KCMIL 350 KCMIL 35 35 60 1.52 2 2 2265 57.54 2362 3515
677834 3 3 400 KCMIL 400 KCMIL 35 35 60 1.52 1 1 2220 56.39 2141 3186
678137 3 3 500 KCMIL 500 KCMIL 35 35 60 1.52 4/0 4/0 2355 59.82 2590 3854
679729 4 4 600 KCMIL 600 KCMIL 58 58 70 1.78 4/0 4/0 2884 73.25 3906 5812
596444 3 3 750 KCMIL 750 KCMIL 58 58 70 1.78 350 350 3061 77.76 3877 5769
678414 4 4 900 KCMIL 900 KCMIL 58 58 70 1.78 1/0 1/0 3308 84.04 5341 7949

Standards & References

Southwire AlumaFlex™ Type MC Cable - PVC Jacketed meets or exceeds the following requirements:

  • UL 83
  • UL 1569
  • UL 1685
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202"(70,000 Btu/hr) Vertical Cable Tray Flame Test
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2, and 3 Hour Through-Penetration FirestopSystems
  • REACH/RoHS-2 (Chemical Limit) Compliant

Construction

Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy - PVC Jacketed is constructed with Aluminum Type THHN/THWN-2 conductors rated 90°C wet or dry, and a bare aluminum grounding conductor for sizes 1/0 AWG and larger. The conductors are cabled together and a binder tape is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly. A black flame retardant sunlight resistant PVC jacket is applied over the armor. The jacket is available in other colors upon request, subject to economic order quantities.

Resources

There are no downloadable resources for this product.