Southwire Armorlite® Type MC Riser Feeder cable is suitable for use as follows:
- Riser cable, vertical applications
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5.
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Conductors are Type THHN/THWN-2 rated 90ºC Wet and Dry. Unjacketed MC cables are not rated for wet locations.
Southwire Armorlite® Type MC Riser Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
| Cond. Size | Conductor Number | Color | Diameter Over Conductor (in) (cm) | Cond. Strands | Insulation Thickness (mils) (mm) | Ground Size | Diameter Over Armor (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
BN,OE,YW,GY
BN,OE,YW,GY
|
0.324
0.82
|
19
19
|
60
1.52
|
1x4
1x4
|
1.818
4.62
|
1195
1778
|
| More Options |
4/0 AWG
4/0 AWG
|
3
3
|
BK,RD,WE
BK,RD,WE
|
0.460
1.17
|
19
19
|
60
1.52
|
1x2
1x2
|
1.943
4.94
|
1445
2150
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
BK,WE,RD,BE
BK,WE,RD,BE
|
0.46
1.17
|
19
19
|
60
1.52
|
1x2
1x2
|
2.106
5.35
|
1811
2695
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
BN,OE,YW,GY
BN,OE,YW,GY
|
0.52
1.32
|
22
22
|
70
1.78
|
1x1
1x1
|
2.243
5.70
|
2105
3133
|
| More Options |
300 KCMIL
300 KCMIL
|
3
3
|
BN,OE,YW
BN,OE,YW
|
0.569
1.45
|
35
35
|
70
1.78
|
1x1
1x1
|
2.093
5.32
|
1858
2765
|
| More Options |
300 KCMIL
300 KCMIL
|
4
4
|
BK,RD,BE,WE
BK,RD,BE,WE
|
0.569
1.45
|
21
21
|
70
1.78
|
1x2
1x2
|
2.286
5.81
|
2296
3417
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
BN,OE,YW,GY
BN,OE,YW,GY
|
0.615
1.56
|
34
34
|
70
1.78
|
1x1/0
1x1/0
|
2.397
6.09
|
2585
3847
|
| More Options |
400 KCMIL
400 KCMIL
|
3
3
|
BN,OE,YW
BN,OE,YW
|
0.659
1.67
|
35
35
|
70
1.78
|
1x3/0
1x3/0
|
2.373
6.03
|
2369
3525
|
| More Options |
500 KCMIL
500 KCMIL
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.735
1.87
|
34
34
|
70
1.78
|
1x2/0
1x2/0
|
2.8
7.11
|
3445
5127
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
BN,OE,YW,GY,GN
BN,OE,YW,GY,GN
|
0.812
2.06
|
41
41
|
80
2.03
|
1x350
1x350
|
3.073
7.81
|
4304
6405
|
| More Options |
750 KCMIL
750 KCMIL
|
3
3
|
BN,OE,YW
BN,OE,YW
|
0.908
2.31
|
58
58
|
80
2.03
|
1x750
1x750
|
3.141
7.98
|
4308
6411
|
| More Options |
750 KCMIL
750 KCMIL
|
4
4
|
BK,RD,BE,WE
BK,RD,BE,WE
|
0.908
2.31
|
58
58
|
80
2.03
|
1x600
1x600
|
3.450
8.76
|
5276
7852
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
1/0 AWG
1/0 AWG
|
4
4
|
12.7
32.26
|
2027
919.43
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
96
96
|
108
108
|
| More Options |
4/0 AWG
4/0 AWG
|
3
3
|
13.6
34.54
|
3808
1727.28
|
0.051
0.08
|
0.061
0.09
|
0.041
0.06
|
180
180
|
205
205
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
14.7
37.34
|
4062
1842.49
|
0.051
0.08
|
0.061
0.09
|
0.041
0.06
|
144
144
|
164
164
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
15.7
39.88
|
6000
2721.55
|
0.071
0.11
|
0.086
0.13
|
0.041
0.06
|
164
164
|
184
184
|
| More Options |
300 KCMIL
300 KCMIL
|
3
3
|
13.7
34.80
|
5400
2449.40
|
0.059
0.09
|
0.071
0.11
|
0.041
0.06
|
230
230
|
260
260
|
| More Options |
300 KCMIL
300 KCMIL
|
4
4
|
16
40.64
|
7200
3265.86
|
0.059
0.09
|
0.071
0.11
|
0.040
0.06
|
184
184
|
208
208
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
16.8
42.67
|
8400
3810.17
|
0.050
0.07
|
0.062
0.09
|
0.040
0.06
|
200
200
|
224
224
|
| More Options |
400 KCMIL
400 KCMIL
|
3
3
|
15.1
38.35
|
7200
3265.86
|
0.044
0.07
|
0.054
0.08
|
0.040
0.06
|
270
270
|
305
305
|
| More Options |
500 KCMIL
500 KCMIL
|
4
4
|
19.6
49.78
|
12000
5443.10
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
248
248
|
280
280
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
21.5
54.61
|
14400
6531.72
|
0.029
0.04
|
0.037
0.06
|
0.039
0.06
|
272
272
|
308
308
|
| More Options |
750 KCMIL
750 KCMIL
|
3
3
|
19.4
49.28
|
13500
6123.49
|
0.024
0.04
|
0.031
0.05
|
0.038
0.06
|
385
385
|
435
435
|
| More Options |
750 KCMIL
750 KCMIL
|
4
4
|
21.3
54.10
|
14400
6531.72
|
0.024
0.04
|
0.031
0.05
|
0.038
0.06
|
308
308
|
348
348
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.