Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
2 AWG
2 AWG
|
7
7
|
0.283
0.72
|
0.551
1.40
|
115
2.92
|
0.611
1.55
|
55
1.40
|
0.761
1.93
|
448
667
|
530
240.40
|
9.1
23.11
|
2
5.08
|
| More Options |
1 AWG
1 AWG
|
19
19
|
0.322
0.82
|
0.59
1.50
|
115
2.92
|
0.65
1.65
|
55
1.40
|
0.8
2.03
|
518
771
|
669
303.45
|
9.6
24.38
|
2
5.08
|
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.362
0.92
|
0.63
1.60
|
115
2.92
|
0.69
1.75
|
80
2.03
|
0.87
2.21
|
626
932
|
844
382.83
|
10.4
26.42
|
2
5.08
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.674
1.71
|
115
2.92
|
0.734
1.86
|
80
2.03
|
0.914
2.32
|
731
1088
|
1064
482.62
|
11
27.94
|
2.5
6.35
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
0.78
1.98
|
115
2.92
|
0.84
2.13
|
80
2.03
|
1.02
2.59
|
1022
1521
|
1692
767.48
|
12.2
30.99
|
2.5
6.35
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
0.834
2.12
|
115
2.92
|
0.894
2.27
|
80
2.03
|
1.074
2.73
|
1167
1737
|
2000
907.18
|
12.9
32.77
|
2.5
6.35
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
0.917
2.33
|
115
2.92
|
0.977
2.48
|
80
2.03
|
1.157
2.94
|
1514
2253
|
2800
1270.06
|
13.9
35.31
|
3
7.62
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.042
2.65
|
115
2.92
|
1.102
2.80
|
80
2.03
|
1.282
3.26
|
2035
3028
|
4000
1814.37
|
15.4
39.12
|
3.5
8.89
|
* Conduit size based on 3 phase 40% fill-factor without ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.221
0.33
|
0.037
0.06
|
0.044
0.07
|
0.566+j0.549
0.566+j0.549
|
0.222+j0.051
0.222+j0.051
|
1924
1924
|
135
135
|
145
145
|
140
140
|
154
154
|
| More Options |
1 AWG
1 AWG
|
0.128
0.19
|
0.175
0.26
|
0.034
0.05
|
0.043
0.06
|
0.524+j0.528
0.524+j0.528
|
0.176+j0.048
0.176+j0.048
|
2045
2045
|
155
155
|
165
165
|
160
160
|
180
180
|
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.139
0.21
|
0.031
0.05
|
0.042
0.06
|
0.492+j0.508
0.492+j0.508
|
0.140+j0.047
0.140+j0.047
|
2169
2169
|
175
175
|
190
190
|
185
185
|
205
205
|
| More Options |
2/0 AWG
2/0 AWG
|
0.082
0.12
|
0.112
0.17
|
0.029
0.04
|
0.040
0.06
|
0.468+j0.487
0.468+j0.487
|
0.113+j0.046
0.113+j0.046
|
2305
2305
|
200
200
|
220
220
|
215
215
|
240
240
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.070
0.10
|
0.024
0.04
|
0.038
0.06
|
0.431+j0.440
0.431+j0.440
|
0.071+j0.043
0.071+j0.043
|
2634
2634
|
265
265
|
280
280
|
285
285
|
320
320
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.059
0.09
|
0.022
0.03
|
0.037
0.06
|
0.420+j0.419
0.420+j0.419
|
0.060+j0.042
0.060+j0.042
|
2801
2801
|
290
290
|
315
315
|
320
320
|
355
355
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.043
0.06
|
0.018
0.03
|
0.035
0.05
|
0.403+j0.387
0.403+j0.387
|
0.044+j0.040
0.044+j0.040
|
3058
3058
|
355
355
|
380
380
|
395
395
|
440
440
|
| More Options |
500 KCMIL
500 KCMIL
|
0.021
0.03
|
0.030
0.04
|
0.015
0.02
|
0.033
0.05
|
0.386+j0.346
0.386+j0.346
|
0.031+j0.038
0.031+j0.038
|
3445
3445
|
430
430
|
460
460
|
485
485
|
545
545
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.