SPEC: 46710

AL Compact 35kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Type MV-105 Single Conductor Aluminum, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, SIMpull Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 35KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications

Select a set of products below for more information:
Cond. Size Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Inner Layer Thickness (mils) (mm) Diameter Over Shield (in) (cm) Outer Layer Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
More Options
1/0 AWG 1/0 AWG
10 10
0.336 0.85
1.214 3.08
420 10.67
1.274 3.24
80 2.03
1.454 3.69
998 1485
633 287.12
17.4 44.20
4.0 10.16
More Options
2/0 AWG 2/0 AWG
12 12
0.376 0.96
1.254 3.19
420 10.67
1.314 3.34
80 2.03
1.494 3.79
1063 1582
798 361.97
17.9 45.47
4.5 11.43
More Options
3/0 AWG 3/0 AWG
15 15
0.422 1.07
1.301 3.30
420 10.67
1.361 3.46
80 2.03
1.541 3.91
1141 1698
1006 456.31
18.4 46.74
4.5 11.43
More Options
4/0 AWG 4/0 AWG
19 19
0.474 1.20
1.353 3.44
420 10.67
1.413 3.59
80 2.03
1.593 4.05
1233 1835
1269 575.61
19.1 48.51
4.5 11.43
More Options
250 KCMIL 250 KCMIL
22 22
0.520 1.32
1.406 3.57
420 10.67
1.466 3.72
80 2.03
1.646 4.18
1323 1969
1500 680.39
19.7 50.04
5.0 12.70
More Options
350 KCMIL 350 KCMIL
35 35
0.615 1.56
1.502 3.82
420 10.67
1.562 3.97
110 2.79
1.802 4.58
1611 2397
2100 952.54
21.6 54.86
5.0 12.70
More Options
500 KCMIL 500 KCMIL
35 35
0.735 1.87
1.644 4.18
420 10.67
1.704 4.33
110 2.79
1.944 4.94
1899 2826
3000 1360.78
23.3 59.18
5.5 13.97
More Options
750 KCMIL 750 KCMIL
58 58
0.908 2.31
1.816 4.61
420 10.67
1.876 4.77
110 2.79
2.126 5.40
2339 3481
4500 2041.16
25.5 64.77
6.0 15.24
More Options
1000 KCMIL 1000 KCMIL
58 58
1.060 2.69
1.968 5.00
420 10.67
2.028 5.15
110 2.79
2.278 5.79
2722 4051
6000 2721.55
27.3 69.34
More Options
1250 KCMIL 1250 KCMIL
91 91
1.250 3.18
2.171 5.51
420 10.67
2.231 5.67
110 2.79
2.471 6.28
3174 4723
7500 3401.94
29.6 75.18

* Strand count meets minimum number per ASTM
! Made with Aluminum 1350

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Capacitive Reactance (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles Allowable Ampacity In Duct 90C Allowable Ampacity In Duct 105C Allowable Ampacity In Air 90C Allowable Ampacity In Air 105C
More Options
1/0 AWG 1/0 AWG
0.168 0.25
0.211 0.31
0.067 0.10
0.055 0.08
0.55 + j0.279 0.55 + j0.279
0.212 + j0.054 0.212 + j0.054
3978 3978
155 155
165 165
200 200
225 225
More Options
2/0 AWG 2/0 AWG
0.133 0.20
0.167 0.25
0.062 0.09
0.053 0.08
0.502 + j0.268 0.502 + j0.268
0.168 + j0.052 0.168 + j0.052
4102 4102
175 175
190 190
230 230
260 260
More Options
3/0 AWG 3/0 AWG
0.105 0.16
0.133 0.20
0.058 0.09
0.051 0.08
0.464 + j0.257 0.464 + j0.257
0.134 + j0.05 0.134 + j0.05
4244 4244
200 200
215 215
270 270
300 300
More Options
4/0 AWG 4/0 AWG
0.084 0.13
0.105 0.16
0.054 0.08
0.050 0.07
0.431 + j0.244 0.431 + j0.244
0.106 + j0.048 0.106 + j0.048
4405 4405
230 230
245 245
310 310
345 345
More Options
250 KCMIL 250 KCMIL
0.071 0.11
0.090 0.13
0.051 0.08
0.048 0.07
0.41 + j0.233 0.41 + j0.233
0.091 + j0.047 0.091 + j0.047
4573 4573
250 250
270 270
345 345
380 380
More Options
350 KCMIL 350 KCMIL
0.050 0.07
0.065 0.10
0.046 0.07
0.046 0.07
0.375 + j0.214 0.375 + j0.214
0.066 + j0.045 0.066 + j0.045
4867 4867
305 305
330 330
430 430
475 475
More Options
500 KCMIL 500 KCMIL
0.035 0.05
0.046 0.07
0.041 0.06
0.044 0.07
0.345 + j0.193 0.345 + j0.193
0.047 + j0.042 0.047 + j0.042
5239 5239
370 370
400 400
530 530
590 590
More Options
750 KCMIL 750 KCMIL
0.024 0.04
0.033 0.05
0.035 0.05
0.041 0.06
0.315 + j0.167 0.315 + j0.167
0.034 + j0.039 0.034 + j0.039
5806 5806
455 455
490 490
685 685
765 765
More Options
1000 KCMIL 1000 KCMIL
0.018 0.03
0.026 0.04
0.031 0.05
0.039 0.06
0.295 + j0.15 0.295 + j0.15
0.027 + j0.038 0.027 + j0.038
6277 6277
525 525
565 565
825 825
920 920
More Options
1250 KCMIL 1250 KCMIL
0.014 0.02
0.023 0.03
0.028 0.04
0.037 0.06
0.276 - j0.124 0.276 - j0.124
0.024 - j0.219 0.024 - j0.219
6878 6878
595 595
640 640
950 950
1055 1055

* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.

Standards & References

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield: Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation: 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level,
  4. Insulation Shield: Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
  6. Overall Jacket: Polyvinyl Chloride (PVC)

Resources