Southwire’s 25KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
Cond. Size (AWG/Kcmil) | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
More Options |
4/0
4/0
|
19
19
|
0.474
1.20
|
1.153
2.93
|
320
8.13
|
1.213
3.08
|
80
2.03
|
1.393
3.54
|
984
1464
|
1269
575.61
|
16.7
42.42
|
4.0
10.16
|
More Options |
750
750
|
53
53
|
0.908
2.31
|
1.616
4.10
|
320
8.13
|
1.676
4.26
|
110
2.79
|
1.926
4.89
|
2005
2984
|
4500
2041.16
|
23.1
58.67
|
5.5
13.97
|
* Strand count meets minimum number per ASTM
Cond. Size (AWG/Kcmil) | DC Resistance @ 25C (ohms/1000') (ohms/km) | AC Resistance @ 75C (ohms/1000') (ohms/km) | Capacitive Reactance (Mohms x 1000ft) (Mohms x km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles (amps) | In Duct Ampacity @ 90C (amps) | In Duct Ampacity @ 105C (amps) | In Air Ampacity @ 90C (amps) | In Air Ampacity @ 105C (amps) | |
More Options |
4/0
4/0
|
0.084
0.13
|
0.105
0.16
|
0.046
0.07
|
0.046
0.07
|
0.45 + j0.285
0.45 + j0.285
|
0.106 + j0.045
0.106 + j0.045
|
3786
3786
|
230
230
|
245
245
|
310
310
|
345
345
|
More Options |
750
750
|
0.024
0.04
|
0.033
0.05
|
0.029
0.04
|
0.039
0.06
|
0.333 + j0.191
0.333 + j0.191
|
0.034 + j0.037
0.034 + j0.037
|
5186
5186
|
455
455
|
490
490
|
685
685
|
765
765
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.