Southwire’s 25KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.336
0.85
|
1.014
2.58
|
320
8.13
|
1.074
2.73
|
80
2.03
|
1.254
3.19
|
771
1147
|
633
287.12
|
15.0
38.10
|
3.5
8.89
|
| More Options |
2/0 AWG
2/0 AWG
|
12
12
|
0.376
0.96
|
1.054
2.68
|
320
8.13
|
1.114
2.83
|
80
2.03
|
1.294
3.29
|
829
1234
|
798
361.97
|
15.5
39.37
|
4.0
10.16
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.474
1.20
|
1.153
2.93
|
320
8.13
|
1.213
3.08
|
80
2.03
|
1.393
3.54
|
984
1464
|
1269
575.61
|
16.7
42.42
|
4.0
10.16
|
| More Options |
500 KCMIL
500 KCMIL
|
34
34
|
0.735
1.87
|
1.444
3.67
|
320
8.13
|
1.504
3.82
|
110
2.79
|
1.744
4.43
|
1593
2371
|
3000
1360.78
|
20.9
53.09
|
5.0
12.70
|
| More Options |
750 KCMIL
750 KCMIL
|
53
53
|
0.908
2.31
|
1.616
4.10
|
320
8.13
|
1.676
4.26
|
110
2.79
|
1.926
4.89
|
2005
2984
|
4500
2041.16
|
23.1
58.67
|
5.5
13.97
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
1/0 AWG
1/0 AWG
|
0.168
0.25
|
0.211
0.31
|
0.057
0.08
|
0.052
0.08
|
0.492 + j0.513
0.492 + j0.513
|
0.128 + j0.038
0.128 + j0.038
|
3358
3358
|
155
155
|
165
165
|
200
200
|
225
225
|
| More Options |
2/0 AWG
2/0 AWG
|
0.133
0.20
|
0.167
0.25
|
0.053
0.08
|
0.050
0.07
|
0.492 + j0.513
0.492 + j0.513
|
0.128 + j0.038
0.128 + j0.038
|
3482
3482
|
175
175
|
190
190
|
230
230
|
260
260
|
| More Options |
4/0 AWG
4/0 AWG
|
0.084
0.13
|
0.105
0.16
|
0.046
0.07
|
0.046
0.07
|
0.492 + j0.513
0.492 + j0.513
|
0.128 + j0.038
0.128 + j0.038
|
3786
3786
|
230
230
|
245
245
|
310
310
|
345
345
|
| More Options |
500 KCMIL
500 KCMIL
|
0.035
0.05
|
0.046
0.07
|
0.034
0.05
|
0.041
0.06
|
0.532 + j0.506
0.532 + j0.506
|
0.167 + j0.037
0.167 + j0.037
|
4619
4619
|
370
370
|
400
400
|
530
530
|
590
590
|
| More Options |
750 KCMIL
750 KCMIL
|
0.024
0.04
|
0.033
0.05
|
0.029
0.04
|
0.039
0.06
|
0.494 + j0.401
0.494 + j0.401
|
0.128 + j0.049
0.128 + j0.049
|
5186
5186
|
455
455
|
490
490
|
685
685
|
765
765
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(12) Detail 1.
* For Free Air: Table 310.60(C)(4).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.