SPEC 44102 3/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Download Category Specifications
PDF Excel Table

Application

Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per Article NEC 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as perminant building wiring. Meets FT-5 Flame Test. cUL listing on select items only.

Specifications

Select a set of products below for more information:
Conductor Allowable Ampacities+ Resistance
Size (AWG or kcmil) (mm2) No. of Strands Nom. OD (Conductor) (mils) (mm) Nom. OD (mils) (mm) Nom. OD (Over Ins.) (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity at 60C Allowable Ampacity at 75C Allowable Ampacity at 90C Insulation Thickness (mils) (mm) Nom. DC Resistance (Conductor) AC Resistance at 90°C
558151
8 AWG 8 AWG
71 71
963 24.46
478 711
48 48
57 57
65 65
60 1.52
0.666 0.666
0.848 0.848
570256
6 AWG 6 AWG
65 65
1030 26.16
609 907
63 63
77 77
87 87
60 1.52
0.415 0.415
0.529 0.529
571409
4 AWG 4 AWG
112 112
1170 29.72
881 1312
84 84
101 101
114 114
60 1.52
0.263 0.263
0.335 0.335
559279
2 AWG 2 AWG
168 168
1292 32.82
1152 1714
112 112
133 133
152 152
60 1.52
0.172 0.172
0.215 0.215
559280
2/0 AWG 2/0 AWG
324 324
1691 42.96
2098 3123
174 174
208 208
237 237
80 2.03
0.0834 0.0834
0.106 0.106
570252
4/0 AWG 4/0 AWG
532 532
1869 47.49
2865 4264
232 232
277 277
316 316
80 2.03
0.0525 0.0525
0.066 0.066
571292
350 KCMIL 350 KCMIL
893 893
2685 68.20
5679 8451
318 318
381 381
433 433
95 2.41
0.032 0.032
0.041 0.041
571442
500 KCMIL 500 KCMIL
1221 1221
2861 72.68
6898 10265
392 392
470 470
536 536
95 2.41
0.0224 0.0224
0.029 0.029

Standards & References

  • ASTM B3: Soft or Annealed Copper Wire
  • ASTM B172: Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650: Standard for Portable Power Cable
  • MSHA: Approved
  • RoHS-2: (European Directive 2011/65/EU)

Construction

  • Conductor: Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  • Separator Tape: Non-conducting tape applied between the conductor and insulation to facilitate stripping
  • Insulation: Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, green.
  • Fillers: Jute fillers applied as needed to round the cable core
  • Reinforcement Binder: Reinforcing binder with twine applied over the core
  • Jacket: Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Resources

There are no downloadable resources for this product.