SPEC: 44102

3/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved SPEC44102

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per Article NEC 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as perminant building wiring. Meets FT-5 Flame Test. cUL listing on select items only.

Specifications

Select a set of products below for more information:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
3 3
71 71
0.145 0.37
60 1.52
145 3.68
0.963 2.45
477 710
More Options
6 AWG 6 AWG
3 3
65 65
0.186 0.47
60 1.52
145 3.68
1.030 2.62
609 906
More Options
4 AWG 4 AWG
3 3
112 112
0.235 0.60
60 1.52
125 3.18
1.170 2.97
881 1311
More Options
2 AWG 2 AWG
3 3
168 168
0.290 0.74
60 1.52
145 3.68
1.292 3.28
1151 1713
More Options
2/0 AWG 2/0 AWG
3 3
324 324
0.400 1.02
80 2.03
155 3.94
1.691 4.30
2098 3122
More Options
4/0 AWG 4/0 AWG
3 3
532 532
0.530 1.35
80 2.03
175 4.45
1.913 4.86
2904 4322
More Options
350 KCMIL 350 KCMIL
3 3
893 893
0.670 1.70
95 2.41
245 6.22
2.685 6.82
5679 8451
More Options
500 KCMIL 500 KCMIL
3 3
1221 1221
0.858 2.18
95 2.41
270 6.86
2.861 7.27
6897 10264
Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Min. Bend Radius (in) (cm) Allowable Ampacity In Air 60C Allowable Ampacity In Air 75C Allowable Ampacity In Air 90C
More Options
8 AWG 8 AWG
0.679 1.01
0.818 1.22
0.052 0.08
3.8 9.65
48 48
57 57
65 65
More Options
6 AWG 6 AWG
0.435 0.65
0.524 0.78
0.051 0.08
5.1 12.95
63 63
77 77
87 87
More Options
4 AWG 4 AWG
0.274 0.41
0.330 0.49
0.048 0.07
5.8 14.73
84 84
101 101
114 114
More Options
2 AWG 2 AWG
0.172 0.26
0.207 0.31
0.045 0.07
6.4 16.26
112 112
133 133
152 152
More Options
2/0 AWG 2/0 AWG
0.087 0.13
0.104 0.15
0.043 0.06
8.4 21.34
174 174
208 208
237 237
More Options
4/0 AWG 4/0 AWG
0.055 0.08
0.067 0.10
0.041 0.06
9.5 24.13
232 232
277 277
316 316
More Options
350 KCMIL 350 KCMIL
0.033 0.05
0.042 0.06
0.040 0.06
16.1 40.89
318 318
381 381
433 433
More Options
500 KCMIL 500 KCMIL
0.023 0.03
0.031 0.05
0.039 0.06
17.1 43.43
392 392
470 470
536 536

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)

Construction

  1. Conductor: Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape: Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation: Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, green.
  4. Fillers: Jute fillers applied as needed to round the cable core
  5. Reinforcement Binder: Reinforcing binder with twine applied over the core
  6. Jacket: Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Resources

There are no downloadable resources for this product.