Predominantly used for underground transmission in conduit systems, suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 345,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.
| Cu Cond, Cu Screen Wires, Cu Laminate | Al Cond, Cu Screen Wires, Al Laminate | ||||||||
| Size (kcmil¹) (mm^2) | Conductor Diameter (inches) (mm) | Insulation Thickness (inch) (cm) | Diameter Over Insulation (inch) (cm) | Overall Jacket Diameter (inch) (cm) | Min. Bend Radius (inch) (inch) | Capacitance | Charging Current (A/kft) | Cable Weight² (lbs/ft) | Cable Weight² (lbs/ft) |
|
1250
31.75
|
1.19
3.02
|
1260
3200.40
|
3.88
9.86
|
4.61
11.71
|
83/56
83/56
|
38.37
38.37
|
3.37
3.37
|
10.81
10.81
|
8.32
8.32
|
|
1500
38.10
|
1.32
3.35
|
1181
2999.74
|
3.85
9.78
|
4.57
11.61
|
83/55
83/55
|
42.75
42.75
|
3.72
3.72
|
11.37
11.37
|
8.34
8.34
|
|
1750
44.45
|
1.43
3.63
|
1142
2900.68
|
3.88
9.86
|
4.61
11.71
|
83/56
83/56
|
45.73
45.73
|
3.98
3.98
|
12.14
12.14
|
8.59
8.59
|
|
2000
50.80
|
1.50
3.81
|
1142
2900.68
|
3.95
10.03
|
4.69
11.91
|
85/57
85/57
|
47.32
47.32
|
4.12
4.12
|
13.08
13.08
|
8.96
8.96
|
|
2500
63.50
|
1.73
4.39
|
1063
2700.02
|
4.05
10.29
|
4.79
12.17
|
87/58
87/58
|
54.58
54.58
|
4.75
4.75
|
14.66
14.66
|
9.51
9.51
|
|
3000
76.20
|
1.89
4.80
|
1063
2700.02
|
4.28
10.87
|
5.03
12.78
|
91/61
91/61
|
59.13
59.13
|
5.15
5.15
|
16.66
16.66
|
10.46
10.46
|
|
3500
88.90
|
2.07
5.26
|
1063
2700.02
|
4.38
11.13
|
5.15
13.08
|
93/62
93/62
|
61.24
61.24
|
5.33
5.33
|
18.42
18.42
|
11.16
11.16
|
|
4000
101.60
|
2.17
5.51
|
1063
2700.02
|
4.48
11.38
|
5.25
13.34
|
95/63
95/63
|
63.19
63.19
|
5.50
5.50
|
20.14
20.14
|
11.83
11.83
|
|
5000
127.00
|
2.48
6.30
|
1063
2700.02
|
4.79
12.17
|
5.59
14.20
|
101/68
101/68
|
69.32
69.32
|
6.04
6.04
|
24.54
24.54
|
13.38
13.38
|
|
6000
152.40
|
2.67
6.78
|
1063
2700.02
|
4.99
12.67
|
5.79
14.71
|
105/70
105/70
|
73.13
73.13
|
6.37
6.37
|
27.30
27.30
|
14.78
14.78
|
| Copper Conductor Size (kcmil¹) Load Factor @ 75% | Aluminum Conductor Size (kcmil¹) Load Factor @ 75% | |||||||
| Size (kcmil¹) (mm^2) | Single Circuit (Amps) | Power Rating (MVA) | Double Circuit (Amps) | Power Rating (MVA) | Single Circuit (Amps) | Power Rating (MVA) | Double Circuit (Amps) | Power Rating (MVA) |
|
1250
31.75
|
920
920
|
637
637
|
770
770
|
533
533
|
730
730
|
506
506
|
620
620
|
430
430
|
|
1500
38.10
|
1010
1010
|
700
700
|
840
840
|
582
582
|
810
810
|
561
561
|
680
680
|
471
471
|
|
1750
44.45
|
1090
1090
|
755
755
|
900
900
|
624
624
|
880
880
|
610
610
|
730
730
|
506
506
|
|
2000
50.80
|
1150
1150
|
797
797
|
950
950
|
658
658
|
940
940
|
651
651
|
780
780
|
540
540
|
|
2500
63.50
|
1370
1370
|
949
949
|
1110
1110
|
769
769
|
1100
1100
|
762
762
|
900
900
|
624
624
|
|
3000
76.20
|
1500
1500
|
1039
1039
|
1220
1220
|
845
845
|
1220
1220
|
845
845
|
980
980
|
679
679
|
|
3500
88.90
|
1600
1600
|
1109
1109
|
1300
1300
|
901
901
|
1320
1320
|
915
915
|
1060
1060
|
734
734
|
|
4000
101.60
|
1700
1700
|
1178
1178
|
1370
1370
|
949
949
|
1410
1410
|
977
977
|
1130
1130
|
783
783
|
|
5000
127.00
|
1880
1880
|
1303
1303
|
1500
1500
|
1039
1039
|
1610
1610
|
1115
1115
|
1290
1290
|
894
894
|
|
6000
152.40
|
2000
2000
|
1386
1386
|
1590
1590
|
1102
1102
|
1770
1770
|
1226
1226
|
1400
1400
|
970
970
|
12500-6000 kcmil conductors are 5 segment Milliken conductors.
2Weight based on screen sized at 279 kcmil which is calculated to accommodate 30 kA for 0.5 sec.
3Based upon single point or cross bonding scheme.
⁴Based on the installation assumptions indicated in the "High Voltage Underground Installation Ratings" located in the Resource Tab