SPEC: 70002

600V ROYAL® SOOW Power Cord Non-UL/CSA with Black Jacket 90°C. MSHA Approved SPEC70002

600 Volt, 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Heat, Moisture and Oil Resistant Flexible CPE Jacket, Non-UL / Non-CSA.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Royal® Non-UL/Non-CSA SOOW cord is designed for use with industrial equipment, heavy tools, battery chargers, portable lights and power extensions, suitable for outdoor applications. The cable is rated -40°C to 90°C, sunlight, water, oil, and weather resistant. Southwire Type SOOW Flexible Cords are permitted for use as specified by Article 400 and related articles of the 2023 National Electrical Code.

Specifications

Select more options below for part numbers, packaging, and color options:
Conductor
Size (AWG or kcmil) (mm2) No. of Conductors No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity Nom. DC Resistance (Conductor) Conductor Colors
More Options
8 AWG 8 AWG
2 2
133 133
615 15.62
218 325
40 40
0.72 0.72
BLACK/WHITE BLACK/WHITE
More Options
8 AWG 8 AWG
3 3
133 133
645 16.38
290 431
40 40
0.72 0.72
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
8 AWG 8 AWG
4 4
133 133
715 18.16
376 560
35 35
0.72 0.72
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
8 AWG 8 AWG
5 5
133 133
834 21.18
492 732
28 28
0.72 0.72
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
6 AWG 6 AWG
2 2
133 133
721 18.31
337 501
55 55
0.4 0.4
BLACK/WHITE BLACK/WHITE
More Options
6 AWG 6 AWG
3 3
133 133
726 18.44
419 624
55 55
0.4 0.4
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
6 AWG 6 AWG
4 4
133 133
803 20.40
539 803
45 45
0.4 0.4
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
6 AWG 6 AWG
5 5
133 133
937 23.80
702 1044
36 36
0.4 0.4
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE
More Options
4 AWG 4 AWG
3 3
133 133
825 20.96
590 878
70 70
0.27 0.27
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
4 AWG 4 AWG
4 4
133 133
950 24.13
762 1134
60 60
0.27 0.27
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
2 AWG 2 AWG
3 3
168 168
1090 27.69
992 1477
95 95
0.16 0.16
BLACK/WHITE/GREEN BLACK/WHITE/GREEN
More Options
2 AWG 2 AWG
4 4
168 168
1290 32.77
1314 1955
80 80
0.16 0.16
BLACK/WHITE/RED/GREEN BLACK/WHITE/RED/GREEN
More Options
2 AWG 2 AWG
5 5
168 168
1373 34.87
1654 2461
64 64
0.16 0.16
BLACK/WHITE/RED/GREEN/ORANGE BLACK/WHITE/RED/GREEN/ORANGE

* Ampacities are based on TABLE 400.5(A)(1) of the 2023 National Electrical Code and CEC Table 12.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • MSHA flame test - P-07-KA190005-MSHA
  • RoHS-3 Complies with European Directive 2015/863
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • Federal Specification J-C-580B

Construction

  1. Conductor:Class K flexible stranded bare copper per ASTM B3 and B174
  2. Insulation:Heat, moisture, and oil resistant EPDM
  3. Filler:Waxed paper fillers
  4. Jacket:Black Chlorinated Polyethylene (CPE) (other colors available upon request)

Resources

There are no downloadable resources for this product.