SPEC: 10000

SIMpull® THHN/THWN-2 Copper SPEC10000

600 Volts Copper Conductor PVC Insulation/Nylon Sheath THHN/THWN-2. Heat, Moisture, Gasoline and Oil Resistant II. SIMpull® Technology for Easier Pulling.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire SIMpull® THHN/THWN-2 copper conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. SIMpull® THHN/THWN-2 copper conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending upon the product application.

Allowable temperatures are as follows:
- THHN or T90 Nylon- Dry locations not to exceed 90°C
- THWN-2: Wet locations not to exceed 90° C
- TWN75- Wet locations not to exceed 75°C
- MTW- Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
- AWM- Dry locations not to exceed 105°C only when rated and used as appliance wiring material

Features

  • Easier pulling with SIMpull NoLube® wire jacket.
  • Stationary package design to further reduce pulling tension.
  • Designed to help lower potential for lifting/handling/pulling injuries.
  • Patented parallel construction to reduce material handling and setup.
  • Avoid broken spools and spool over-turn.
  • Specifications

    Select more options below for part numbers, packaging, and color options:
    Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
    More Options
    8 AWG 8 AWG
    1 1
    19 19
    0.143 0.36
    31 0.79
    6 0.15
    0.217 0.55
    50 74
    63 94
    More Options
    6 AWG 6 AWG
    1 1
    19 19
    0.179 0.45
    31 0.79
    0.241 0.61
    6 0.15
    0.253 0.64
    81 121
    95 141
    More Options
    4 AWG 4 AWG
    1 1
    19 19
    0.226 0.57
    42 1.07
    0.31 0.79
    7 0.18
    0.324 0.82
    128 190
    153 228
    More Options
    3 AWG 3 AWG
    1 1
    19 19
    0.254 0.65
    42 1.07
    0.338 0.86
    7 0.18
    0.35 0.89
    162 241
    189 281
    More Options
    2 AWG 2 AWG
    1 1
    19 19
    0.286 0.73
    42 1.07
    0.37 0.94
    7 0.18
    0.384 0.98
    204 304
    235 350
    More Options
    1 AWG 1 AWG
    1 1
    19 19
    0.322 0.82
    52 1.32
    0.426 1.08
    8 0.20
    0.441 1.12
    258 384
    301 448
    More Options
    1/0 AWG 1/0 AWG
    1 1
    19 19
    0.362 0.92
    52 1.32
    0.466 1.18
    8 0.20
    0.48 1.22
    326 485
    374 557
    More Options
    2/0 AWG 2/0 AWG
    1 1
    19 19
    0.405 1.03
    52 1.32
    0.509 1.29
    8 0.20
    0.524 1.33
    410 610
    464 691
    More Options
    3/0 AWG 3/0 AWG
    1 1
    19 19
    0.456 1.16
    52 1.32
    0.56 1.42
    8 0.20
    0.574 1.46
    518 771
    578 860
    More Options
    4/0 AWG 4/0 AWG
    1 1
    19 19
    0.512 1.30
    52 1.32
    0.616 1.56
    8 0.20
    0.618 1.57
    653 972
    719 1070
    More Options
    250 KCMIL 250 KCMIL
    1 1
    37 37
    0.558 1.42
    62 1.57
    0.682 1.73
    9 0.23
    0.684 1.74
    771 1147
    844 1256
    More Options
    300 KCMIL 300 KCMIL
    1 1
    37 37
    0.611 1.55
    62 1.57
    0.735 1.87
    9 0.23
    0.736 1.87
    926 1378
    1016 1512
    More Options
    350 KCMIL 350 KCMIL
    1 1
    37 37
    0.661 1.68
    62 1.57
    0.785 1.99
    9 0.23
    0.783 1.99
    1080 1607
    1180 1756
    More Options
    400 KCMIL 400 KCMIL
    1 1
    37 37
    0.706 1.79
    62 1.57
    0.83 2.11
    9 0.23
    0.827 2.10
    1235 1838
    1341 1996
    More Options
    500 KCMIL 500 KCMIL
    1 1
    37 37
    0.789 2.00
    62 1.57
    0.913 2.32
    9 0.23
    0.908 2.31
    1543 2296
    1662 2473
    More Options
    600 KCMIL 600 KCMIL
    1 1
    61 61
    0.866 2.20
    72 1.83
    1.01 2.57
    10 0.25
    1.004 2.55
    1852 2756
    1992 2964
    More Options
    750 KCMIL 750 KCMIL
    1 1
    61 61
    0.968 2.46
    72 1.83
    1.112 2.82
    10 0.25
    1.103 2.80
    2315 3445
    2470 3676
    More Options
    1000 KCMIL 1000 KCMIL
    1 1
    61 61
    1.117 2.84
    72 1.83
    1.261 3.20
    10 0.25
    1.281 3.25
    3087 4594
    3264 4857
    Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
    More Options
    8 AWG 8 AWG
    1 1
    0.9 2.29
    132 59.87
    0.653 0.97
    0.810 1.21
    0.052 0.08
    50 50
    55 55
    More Options
    6 AWG 6 AWG
    1 1
    1 2.54
    209 94.80
    0.411 0.61
    0.510 0.76
    0.051 0.08
    65 65
    75 75
    More Options
    4 AWG 4 AWG
    1 1
    1.3 3.30
    333 151.05
    0.258 0.38
    0.320 0.48
    0.048 0.07
    85 85
    95 95
    More Options
    3 AWG 3 AWG
    1 1
    1.4 3.56
    420 190.51
    0.205 0.31
    0.254 0.38
    0.047 0.07
    100 100
    115 115
    More Options
    2 AWG 2 AWG
    1 1
    1.5 3.81
    530 240.40
    0.162 0.24
    0.201 0.30
    0.045 0.07
    115 115
    130 130
    More Options
    1 AWG 1 AWG
    1 1
    1.8 4.57
    669 303.45
    0.128 0.19
    0.159 0.24
    0.046 0.07
    130 130
    145 145
    More Options
    1/0 AWG 1/0 AWG
    1 1
    1.9 4.83
    844 382.83
    0.102 0.15
    0.127 0.19
    0.044 0.07
    150 150
    170 170
    More Options
    2/0 AWG 2/0 AWG
    1 1
    2.1 5.33
    1064 482.62
    0.082 0.12
    0.102 0.15
    0.043 0.06
    175 175
    195 195
    More Options
    3/0 AWG 3/0 AWG
    1 1
    2.3 5.84
    1342 608.72
    0.064 0.10
    0.079 0.12
    0.042 0.06
    200 200
    225 225
    More Options
    4/0 AWG 4/0 AWG
    1 1
    2.5 6.35
    1692 767.48
    0.051 0.08
    0.063 0.09
    0.041 0.06
    230 230
    260 260
    More Options
    250 KCMIL 250 KCMIL
    1 1
    2.7 6.86
    2000 907.18
    0.043 0.06
    0.053 0.08
    0.041 0.06
    255 255
    290 290
    More Options
    300 KCMIL 300 KCMIL
    1 1
    2.9 7.37
    2400 1088.62
    0.036 0.05
    0.045 0.07
    0.041 0.06
    285 285
    320 320
    More Options
    350 KCMIL 350 KCMIL
    1 1
    3.1 7.87
    2800 1270.06
    0.031 0.05
    0.039 0.06
    0.040 0.06
    310 310
    350 350
    More Options
    400 KCMIL 400 KCMIL
    1 1
    3.3 8.38
    3200 1451.49
    0.027 0.04
    0.035 0.05
    0.040 0.06
    335 335
    380 380
    More Options
    500 KCMIL 500 KCMIL
    1 1
    3.6 9.14
    4000 1814.37
    0.021 0.03
    0.027 0.04
    0.039 0.06
    380 380
    430 430
    More Options
    600 KCMIL 600 KCMIL
    1 1
    5 12.70
    4800 2177.24
    0.018 0.03
    0.024 0.04
    0.039 0.06
    420 420
    475 475
    More Options
    750 KCMIL 750 KCMIL
    1 1
    5.5 13.97
    6000 2721.55
    0.014 0.02
    0.019 0.03
    0.038 0.06
    475 475
    535 535
    More Options
    1000 KCMIL 1000 KCMIL
    1 1
    6.4 16.26
    8000 3628.74
    0.011 0.02
    0.016 0.02
    0.037 0.06
    545 545
    615 615

    Notes:
    1) Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    2) Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center
    3) There is no need to look up the minimum bending radius value on this spec sheet if you purchase Southwire’s Patent Pending Re3™ Minimum Bend Radius Device: SPEC 11123

    Size (Strand) Black Red Blue White Brown Orange Yellow Gray Green Purple
    8 (19) 8 (19)
    204883
    204909
    204917
    204891
    238477
    238493
    238485
    238501
    204925
    256586
    6 (19) 6 (19)
    204933
    204958
    204966
    204941
    260695
    260679
    260687
    254649
    204974
    485607
    4 (19) 4 (19)
    204990
    204982
    205633
    205005
    411702
    411710
    411694
    611778
    251728
    552486
    3 (19) 3 (19)
    243469
    243485
    372763
    243477
    551078
    551079
    551080
    551081
    601971
    552533
    2 (19) 2 (19)
    205021
    205013
    315812
    205039
    610169
    610171
    420653
    610172
    295832
    552534
    1 (19) 1 (19)
    205047
    344598
    481945
    344580
    550890
    550888
    550887
    550891
    400192
    552488
    1/0 (19) 1/0 (19)
    205054
    558773
    558774
    558771
    558778
    558779
    558777
    558781
    556315
    551539
    2/0 (19) 2/0 (19)
    205062
    556113
    556114
    556111
    556119
    556117
    556116
    558784
    556115
    552535
    3/0 (19) 3/0 (19)
    205070
    556121
    556122
    556120
    556127
    556125
    556124
    556698
    556123
    551541
    4/0 (19) 4/0 (19)
    205088
    556129
    556130
    556128
    556135
    556133
    556132
    556697
    556131
    551540
    250 (37) 250 (37)
    205096
    556137
    556138
    556136
    556143
    556141
    556140
    556552
    556139
    551025
    300 (37) 300 (37)
    205104
    556145
    556146
    556144
    556150
    556149
    556148
    556551
    556147
    551026
    350 (37) 350 (37)
    205112
    556152
    556153
    556151
    556157
    556156
    556155
    556707
    556154
    551027
    400 (37) 400 (37)
    205120
    556160
    556161
    556158
    556165
    556164
    556163
    556550
    556162
    551029
    500 (37) 500 (37)
    205138
    556168
    556169
    556166
    556173
    556172
    556171
    556549
    556170
    551599
    600 (61) 600 (61)
    321471
    556176
    556177
    556174
    556181
    556180
    556179
    558859
    556178
    552485
    750 (61) 750 (61)
    320994
    564946
    564944
    564945
    550909
    550908
    550907
    550910
    551700
    552536
    1000 (61) 1000 (61)
    289710
    552644
    552645
    552647
    564234
    Size (Strand) Pink Tan White/Red Gray/Purple Gray/Orange Gray/Yellow Gray/Brown Green/Yellow White/Blue White/Black
    8 (19) 8 (19)
    570785
    597981
    6 (19) 6 (19)
    578288
    578287
    4 (19) 4 (19)
    597980
    597979
    3 (19) 3 (19)
    597978
    597977
    679383 679383
    2 (19) 2 (19)
    458399
    1 (19) 1 (19)
    578284
    578285
    679438 679438
    1/0 (19) 1/0 (19)
    597975
    597976
    678121
    2/0 (19) 2/0 (19)
    647637
    647638
    674310
    3/0 (19) 3/0 (19)
    679272
    679273
    677828 677828
    679380 679380
    4/0 (19) 4/0 (19)
    551059
    568845
    679379
    250 (37) 250 (37)
    592681
    592682
    678119
    646952 646952
    300 (37) 300 (37)
    578109
    578110
    350 (37) 350 (37)
    586062
    586063
    678120
    679458 679458
    400 (37) 400 (37)
    581797
    581798
    674311
    500 (37) 500 (37)
    581782
    581783
    671509
    600 (61) 600 (61)
    560486
    560487
    664610
    750 (61) 750 (61)
    597954
    597955
    1000 (61) 1000 (61)

    Standards & References

    • ASTM B3 Soft or Annealed Copper Wire
    • ASTM B8 Concentric-Lay-Stranded Copper Conductors
    • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
    • UL 83 Thermoplastic Insulated Wires and Cables
    • UL 758 Standard for Appliance Wiring Material
    • UL 1063 Machine Tool Wiring (MTW)
    • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
    • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
    • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
    • Federal Specification A-A-59544
    • NMX-J-010-ANCE Thermoplastic insulated wires and cables
    • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
    • NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable
    • NFPA 70®, National Electrical Code® (NEC®)

    Construction

    1. Conductor: Sizes 8 - 3/0 AWG use a stranded combination-unilay soft drawn annealed bare copper per ASTM B3 and B787. Sizes 4/0 AWG and larger use a stranded compressed annealed bare copper per ASTM B3 and B8.
    2. Insulation:Heat and moisture resistant Polyvinyl Chloride (PVC)
    3. Sheath:Nylon jacket utilizing SIMpull® Technology