SPEC: 10025

SIMpull CoilPAK™ Wire Payoff THHN/THWN-2 Copper SPEC10025

Work smarter with the SIMpull CoilPAK™ Wire Payoff by reducing the physical effort associated with material handling, setup, and pulling compared to traditional spools, increasing both safety and productivity on the job. Copper, 600 Volt, Type THHN/THWN-2

Download Category Specifications
PDF Excel Table

Application & Features

The SIMpull CoilPAK™ Wire Payoff provides greater versatility and efficiency to branch circuit installations, eliminating the need for handling bulky spools and all the setup and energy that go along with them. SIMpull CoilPAK™ Wire Payoffs increase both safety and productivity by reducing the physical effort associated with material handling, pulling wire out of the package, and pulling wire through conduit. SIMpull CoilPAK™ THHN/THWN-2 copper conductors are primarily used in conduit for branch circuits in commercial or industrial applications as specified in the National Electrical Code® and other applicable codes and standards. Voltage for all applications is 600 volts. SIMpull CoilPAK™ THHN/THWN-2 copper conductors are designed to be installed without the application of a pulling lubricant. These conductors have multiple ratings depending upon the product application.

Allowable temperatures are as follows:
• THHN or T90 Nylon - Dry locations not to exceed 90°C
• THWN-2 - Wet or dry locations not to exceed 90°C or locations not to exceed 75°C when exposed to oil
• TWN75 - Wet locations not to exceed 75°C
• MTW - Wet locations or when exposed to oil at temperatures not to exceed 60°C or dry locations not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79)
• AWM - Dry locations not to exceed 105°C only when rated and used as appliance wiring material

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
14 AWG 14 AWG
1 1
SOLID SOLID
0.064 0.16
16 0.41
0.096 0.24
5 0.13
0.106 0.27
12 18
15 22
More Options
14 AWG 14 AWG
1 1
19 19
0.073 0.19
16 0.41
0.105 0.27
5 0.13
0.113 0.29
12 18
16 24
More Options
null AWG null AWG
More Options
null AWG null AWG
More Options
12 AWG 12 AWG
1 1
SOLID SOLID
0.081 0.21
16 0.41
0.113 0.29
5 0.13
0.123 0.31
19 28
23 34
More Options
12 AWG 12 AWG
1 1
19 19
0.09 0.23
16 0.41
0.122 0.31
5 0.13
0.132 0.34
20 30
24 36
More Options
12 AWG 12 AWG
2 2
SOLID SOLID
0.081 0.21
16 0.41
0.113 0.29
5 0.13
0.246 0.62
38 57
46 68
More Options
12 AWG 12 AWG
2 2
19 19
0.09 0.23
16 0.41
0.122 0.31
5 0.13
0.264 0.67
40 60
48 71
More Options
12 AWG 12 AWG
3 3
SOLID SOLID
0.081 0.21
16 0.41
0.113 0.29
5 0.13
0.266 0.68
57 85
69 103
More Options
12 AWG 12 AWG
3 3
19 19
0.09 0.23
16 0.41
0.122 0.31
5 0.13
0.285 0.72
60 89
72 107
More Options
12 AWG 12 AWG
4 4
19 19
0.09 0.23
16 0.41
0.122 0.31
5 0.13
0.319 0.81
80 119
96 143
More Options
10 AWG 10 AWG
1 1
SOLID SOLID
0.101 0.26
21 0.53
0.144 0.37
5 0.13
0.154 0.39
30 45
36 54
More Options
10 AWG 10 AWG
1 1
19 19
0.117 0.30
21 0.53
0.157 0.40
5 0.13
0.165 0.42
32 48
38 57
More Options
10 AWG 10 AWG
2 2
SOLID SOLID
0.101 0.26
21 0.53
0.144 0.37
5 0.13
0.308 0.78
60 89
72 107
More Options
10 AWG 10 AWG
2 2
19 19
0.117 0.30
21 0.53
0.157 0.40
5 0.13
0.33 0.84
64 95
76 113
More Options
10 AWG 10 AWG
3 3
19 19
0.117 0.30
21 0.53
0.157 0.40
5 0.13
0.356 0.90
96 143
114 170
More Options
10 AWG 10 AWG
4 4
19 19
0.117 0.30
21 0.53
0.157 0.40
5 0.13
0.37 0.94
128 190
152 226

• TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
14 AWG 14 AWG
1 1
0.4 1.02
2.631 3.92
3.265 4.86
0.058 0.09
20 20
25 25
More Options
14 AWG 14 AWG
1 1
0.5 1.27
2.631 3.92
3.265 4.86
0.058 0.09
20 20
25 25
More Options
null AWG null AWG
More Options
null AWG null AWG
More Options
12 AWG 12 AWG
1 1
0.5 1.27
1.662 2.47
2.063 3.07
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
1 1
0.5 1.27
1.662 2.47
2.063 3.07
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
2 2
1 2.54
1.662 2.47
2.063 3.07
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
2 2
1.1 2.79
1.662 2.47
2.063 3.07
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
3 3
1.1 2.79
1.662 2.47
2.063 3.07
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
3 3
1.1 2.79
1.662 2.47
2.063 3.07
0.054 0.08
25 25
30 30
More Options
12 AWG 12 AWG
4 4
1.3 3.30
1.662 2.47
2.063 3.07
0.054 0.08
20 20
24 24
More Options
10 AWG 10 AWG
1 1
0.6 1.52
1.040 1.55
1.291 1.92
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
1 1
0.7 1.78
1.040 1.55
1.291 1.92
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
2 2
1.2 3.05
1.040 1.55
1.291 1.92
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
2 2
1.3 3.30
1.040 1.55
1.291 1.92
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
3 3
1.4 3.56
1.040 1.55
1.291 1.92
0.050 0.07
35 35
40 40
More Options
10 AWG 10 AWG
4 4
1.5 3.81
1.040 1.55
1.291 1.92
0.050 0.07
28 28
32 32

• Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
• Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (Strand) Cond. Number Blue Black Brown Green Green/Yellow Gray Gray/Brown Gray/Orange Gray/Purple Gray/Yellow
14 (Solid) 14 (Solid)
1 1
58028705
58028505
58028805
58029105
58028905
14 (19) 14 (19)
1 1
58017105
58017005
58017205
58017605
58017305
12 (Solid) 12 (Solid)
1 1
58026705
58026505
58026805
58027105
58456605
58026905
58027705
58027805
58026305
58027905
12 (19) 12 (19)
1 1
58018405
58018205
58018505
58019505
58386305
58018605
58018705
58018905
58018805
58019005
10 (Solid) 10 (Solid)
1 1
58020405
58020305
58020505
58021105
58021205
58020605
58022605
58020805
58021005
10 (19) 10 (19)
1 1
58022205
58022105
58022305
58025105
58456705
58025005
58020705
58025705
58022705
58025905
Size (Strand) Cond. Number Orange Purple Pink Red Tan White White/Blue White/Black White/Red Yellow
14 (Solid) 14 (Solid)
1 1
58029205
58028605
58029305
58029405
58029505
14 (19) 14 (19)
1 1
58017705
58017805
58193305
58017905
58018005
58018105
12 (Solid) 12 (Solid)
1 1
58027205
58026405
58193105
58027305
58027505
58028105
58028005
58028305
58027605
12 (19) 12 (19)
1 1
58019605
58019705
58193205
58019805
58019905
58019305
58019205
58019405
58020005
10 (Solid) 10 (Solid)
1 1
58021305
58020205
58021405
58021505
58021805
58021605
58021905
58022005
10 (19) 10 (19)
1 1
58025205
58025305
58193005
58025405
59805002
58025505
58026105
58026005
58026205
58025605
Size (Strand) Cond. Number Blue, White/Blue Black, Red Black, White/Black Brown, Gray/Brown Orange, Gray/Orange Red, White/Red Yellow, Gray/Yellow Brown, Orange, Yellow Black, Red, Green Black, White, Green Brown, Orange, Yellow, Green Purple, Gray/Purple
12 (Solid) 12 (Solid)
2 2
58614501
58619401
58619501
58614701
58614401
58614801
139369 139369
12 (19) 12 (19)
2 2
58609701
58609501
58612001
58610001
58609601
58610101
10 (Solid) 10 (Solid)
2 2
58105005
58029705
58920505
58920705
58105505
58920605
10 (19) 10 (19)
2 2
58725401
59306201
58725101
58725701
58725501
58725201
58725601
14 (Solid) 14 (Solid)
3 3
59318001
14 (19) 14 (19)
3 3
59318101
12 (Solid) 12 (Solid)
3 3
58389701
12 (19) 12 (19)
3 3
58453301
10 (19) 10 (19)
3 3
58114302
59799501
12 (19) 12 (19)
4 4
58139402
10 (19) 10 (19)
4 4
58138504
Size (Strand) Cond. Number Blue Black Brown Green Green/Yellow Gray
12 (Solid) 12 (Solid)
1 1
58026704
58026504
58026804
58027104
58456604 58456604
58026904
12 (19) 12 (19)
1 1
58018404
58018204
58018504
58019504
58386304 58386304
58018604
Size (Strand) Cond. Number Orange Purple Pink Red White White/Blue White/Black White/Red Yellow
12 (Solid) 12 (Solid)
1 1
58027204
58027304
58027504
58028104
58028004
58028304
58027604
12 (19) 12 (19)
1 1
58019604
58019704
58193204
58019804
58019904
58019304
58019204
58019404
58020004
Size (Strand) Cond. Number Blue, White/Blue Black, White/Black Brown, Gray/Brown Orange, Gray/Orange Red, White/Red Yellow, Gray/Yellow Black, White, Green
12 (Solid) 12 (Solid)
2 2
58614504
58619404
58614404
12 (19) 12 (19)
2 2
58609704
58609504
58612004 58612004
58610004 58610004
58609604
58610104
12 (Solid) 12 (Solid)
3 3
58389703
12 (19) 12 (19)
3 3
58453303
Size (Strand) Cond. Number PhaseID Black, White/Black Red, White/Red Blue, White/Blue Brown, Gray/Brown Orange, Gray/Orange Yellow, Gray/Yellow
10 (19) 10 (19)
2 2
1-ONE 1-ONE
66551601 66551601
66551701 66551701
66551801 66551801
66551901 66551901
66552101 66552101
66552201 66552201
10 (19) 10 (19)
2 2
2-TWO 2-TWO
51652301 51652301
51652401 51652401
51652501 51652501
10 (19) 10 (19)
2 2
3-THREE 3-THREE
51652601 51652601
51652701 51652701
51652801 51652801

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • NMX-J-010-ANCE Thermoplastic insulated wires and cables
  • NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
  • NEMA 70901-2-2024 Make It American Compliance with Domestic Preference Requirements Pt. 2 Wire & Cable

Construction

  1. Conductor: Solid, soft drawn, annealed, bare copper per ASTM B3 or combination-unilay, Class C, stranded soft drawn annealed bare copper per ASTM B3 and B787
  2. Insulation: Heat and moisture resistant Polyvinyl Chloride (PVC) insulation in various colors
  3. Sheath: Nylon jacket utilizing SIMpull® Technology

• For information about our SIMpull CoilPAK™ Wire Payoff please visit us at:   SIMpull CoilPAK™ Wire Payoff