Southwire Type SER, service entrance cable is primarily used to convey power from the service drop to the meter base and from the meter base to the distribution panelboard; however, the cable may be used in all applications where Type SE cable is permitted. SER may be used in wet or dry locations at temperatures not to exceed 90°C. Voltage rating is 600 volts. SE cables are not permitted underground, with or without a raceway, per NEC 338.12(A)(2).
| Cond. Size | Conductor Number | Diameter Over Conductor (in) (cm) | Cond. Strands | Insulation Thickness (mils) (mm) | Ground Size | Num x Neutral Size | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
6 AWG
6 AWG
|
3
3
|
0.177
0.45
|
7
7
|
45
1.14
|
1x6
1x6
|
1x6
1x6
|
30
0.76
|
0.710
1.80
|
421
627
|
| More Options |
4 AWG
4 AWG
|
3
3
|
0.225
0.57
|
7
7
|
45
1.14
|
1x6
1x6
|
1x6
1x6
|
30
0.76
|
0.787
2.00
|
584
869
|
| More Options |
3 AWG
3 AWG
|
3
3
|
0.252
0.64
|
7
7
|
45
1.14
|
1x5
1x5
|
1x5
1x5
|
30
0.76
|
0.855
2.17
|
718
1069
|
| More Options |
2 AWG
2 AWG
|
3
3
|
0.282
0.72
|
7
7
|
45
1.14
|
1x4
1x4
|
1x4
1x4
|
30
0.76
|
0.933
2.37
|
886
1319
|
| More Options |
1 AWG
1 AWG
|
3
3
|
0.322
0.82
|
19
19
|
55
1.40
|
1x3
1x3
|
1x3
1x3
|
30
0.76
|
1.131
2.87
|
1124
1673
|
| More Options |
1/0 AWG
1/0 AWG
|
3
3
|
0.361
0.92
|
19
19
|
55
1.40
|
1x2
1x2
|
1x2
1x2
|
30
0.76
|
1.240
3.15
|
1395
2076
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
0.405
1.03
|
19
19
|
55
1.40
|
1x1
1x1
|
1x1
1x1
|
30
0.76
|
1.346
3.42
|
1730
2575
|
| More Options |
3/0 AWG
3/0 AWG
|
3
3
|
0.456
1.16
|
19
19
|
55
1.40
|
1x1/0
1x1/0
|
1x1/0
1x1/0
|
30
0.76
|
1.462
3.71
|
2149
3198
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Neutral Stranding (mils) (mm) | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
6 AWG
6 AWG
|
3
3
|
|
2.8
7.11
|
629
285.31
|
0.411
0.61
|
0.495
0.74
|
0.051
0.08
|
65
65
|
75
75
|
| More Options |
4 AWG
4 AWG
|
3
3
|
1
0.03
|
3.1
7.87
|
1001
454.05
|
0.258
0.38
|
0.310
0.46
|
0.048
0.07
|
85
85
|
95
95
|
| More Options |
3 AWG
3 AWG
|
3
3
|
1
0.03
|
3.4
8.64
|
1262
572.43
|
0.205
0.31
|
0.246
0.37
|
0.047
0.07
|
100
100
|
115
115
|
| More Options |
2 AWG
2 AWG
|
3
3
|
1
0.03
|
3.7
9.40
|
1592
722.12
|
0.162
0.24
|
0.195
0.29
|
0.045
0.07
|
115
115
|
130
130
|
| More Options |
1 AWG
1 AWG
|
3
3
|
1
0.03
|
5.7
14.48
|
2008
910.81
|
0.128
0.19
|
0.154
0.23
|
0.046
0.07
|
130
130
|
145
145
|
| More Options |
1/0 AWG
1/0 AWG
|
3
3
|
1
0.03
|
6.2
15.75
|
2534
1149.40
|
0.102
0.15
|
0.122
0.18
|
0.044
0.07
|
150
150
|
170
170
|
| More Options |
2/0 AWG
2/0 AWG
|
3
3
|
1
0.03
|
6.7
17.02
|
3194
1448.77
|
0.081
0.12
|
0.097
0.14
|
0.043
0.06
|
175
175
|
195
195
|
| More Options |
3/0 AWG
3/0 AWG
|
3
3
|
1
0.03
|
7.3
18.54
|
4027
1826.61
|
0.064
0.10
|
0.078
0.12
|
0.042
0.06
|
200
200
|
225
225
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.