Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
2 AWG
2 AWG
|
7
7
|
0.283
0.72
|
0.551
1.40
|
115
2.92
|
0.611
1.55
|
1x6
1x6
|
80
2.03
|
1.797
4.56
|
65
1.65
|
1.929
4.90
|
1925
2865
|
1592
722.12
|
13.5
34.29
|
2.5
6.35
|
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.362
0.92
|
0.63
1.60
|
115
2.92
|
0.69
1.75
|
1x6
1x6
|
110
2.79
|
2.104
5.34
|
60
1.52
|
2.224
5.65
|
2824
4203
|
2534
1149.40
|
15.6
39.62
|
3
7.62
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.673
1.71
|
115
2.92
|
0.733
1.86
|
1x4
1x4
|
110
2.79
|
2.081
5.29
|
65
1.65
|
2.213
5.62
|
2893
4305
|
3194
1448.77
|
15.5
39.37
|
3
7.62
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
0.834
2.12
|
115
2.92
|
0.894
2.27
|
1x4
1x4
|
110
2.79
|
2.545
6.46
|
75
1.91
|
2.695
6.85
|
4827
7183
|
6000
2721.55
|
18.9
48.01
|
3.5
8.89
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
0.917
2.33
|
115
2.92
|
0.977
2.48
|
1x3
1x3
|
110
2.79
|
2.724
6.92
|
75
1.91
|
2.874
7.30
|
6044
8994
|
8400
3810.17
|
20.1
51.05
|
3.5
8.89
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.042
2.65
|
115
2.92
|
1.102
2.80
|
1x3
1x3
|
110
2.79
|
2.994
7.60
|
75
1.91
|
3.144
7.99
|
7807
11618
|
12000
5443.10
|
22
55.88
|
4
10.16
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.254
3.19
|
115
2.92
|
1.314
3.34
|
1x2
1x2
|
125
3.18
|
3.502
8.90
|
85
2.16
|
3.672
9.33
|
11077
16484
|
18000
8164.66
|
25.7
65.28
|
5
12.70
|
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^Yellow outer jacket
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.221
0.33
|
0.028
0.04
|
0.024
0.04
|
0.577+j0.556
0.577+j0.556
|
0.221+j0.041
0.221+j0.041
|
1924
1924
|
201
201
|
172
172
|
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.139
0.21
|
0.024
0.04
|
0.021
0.03
|
0.503+j0.513
0.503+j0.513
|
0.139+j0.037
0.139+j0.037
|
2169
2169
|
257
257
|
225
225
|
| More Options |
2/0 AWG
2/0 AWG
|
0.082
0.12
|
0.112
0.17
|
0.022
0.03
|
0.020
0.03
|
0.479+j0.492
0.479+j0.492
|
0.112+j0.036
0.112+j0.036
|
2302
2302
|
292
292
|
260
260
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.059
0.09
|
0.017
0.03
|
0.017
0.03
|
0.430+j0.421
0.430+j0.421
|
0.059+j0.033
0.059+j0.033
|
2801
2801
|
410
410
|
376
376
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.043
0.06
|
0.014
0.02
|
0.015
0.02
|
0.412+j0.389
0.412+j0.389
|
0.043+j0.031
0.043+j0.031
|
3058
3058
|
487
487
|
460
460
|
| More Options |
500 KCMIL
500 KCMIL
|
0.021
0.03
|
0.030
0.04
|
0.012
0.02
|
0.014
0.02
|
0.394+j0.347
0.394+j0.347
|
0.030+j0.030
0.030+j0.030
|
3445
3445
|
573
573
|
556
556
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.021
0.03
|
0.011
0.02
|
0.013
0.02
|
0.370+j0.288
0.370+j0.288
|
0.021+j0.029
0.021+j0.029
|
4102
4102
|
668
668
|
678
678
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
* Ampacities are based on Table D17N of the Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
* Ampacities are based on Table D17E of the Canadian Electrical Code Part I
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E