SPEC: 26142

HVTECK CU 3/C 115NLEPR TS PVC AIA PVC 5kV 133% CSA SPEC26142

3 Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Cond. Strands Diameter Over Conductor (in) (cm) Diameter Over Insulation (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Shield (in) (cm) Ground Size Inner Jacket Thickness (mils) (mm) Diameter Over Armor (in) (cm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Conduit Size (in) (cm)
More Options
2 AWG 2 AWG
7 7
0.283 0.72
0.551 1.40
115 2.92
0.611 1.55
1x6 1x6
80 2.03
1.797 4.56
65 1.65
1.929 4.90
1925 2865
1592 722.12
13.5 34.29
2.5 6.35
More Options
1/0 AWG 1/0 AWG
19 19
0.362 0.92
0.63 1.60
115 2.92
0.69 1.75
1x6 1x6
110 2.79
2.104 5.34
60 1.52
2.224 5.65
2824 4203
2534 1149.40
15.6 39.62
3 7.62
More Options
2/0 AWG 2/0 AWG
19 19
0.405 1.03
0.673 1.71
115 2.92
0.733 1.86
1x4 1x4
110 2.79
2.081 5.29
65 1.65
2.213 5.62
2893 4305
3194 1448.77
15.5 39.37
3 7.62
More Options
250 KCMIL 250 KCMIL
37 37
0.558 1.42
0.834 2.12
115 2.92
0.894 2.27
1x4 1x4
110 2.79
2.545 6.46
75 1.91
2.695 6.85
4827 7183
6000 2721.55
18.9 48.01
3.5 8.89
More Options
350 KCMIL 350 KCMIL
37 37
0.661 1.68
0.917 2.33
115 2.92
0.977 2.48
1x3 1x3
110 2.79
2.724 6.92
75 1.91
2.874 7.30
6044 8994
8400 3810.17
20.1 51.05
3.5 8.89
More Options
500 KCMIL 500 KCMIL
37 37
0.789 2.00
1.042 2.65
115 2.92
1.102 2.80
1x3 1x3
110 2.79
2.994 7.60
75 1.91
3.144 7.99
7807 11618
12000 5443.10
22 55.88
4 10.16
More Options
750 KCMIL 750 KCMIL
61 61
0.968 2.46
1.254 3.19
115 2.92
1.314 3.34
1x2 1x2
125 3.18
3.502 8.90
85 2.16
3.672 9.33
11077 16484
18000 8164.66
25.7 65.28
5 12.70

1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^Yellow outer jacket
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Capacitive Reactance (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Zero Sequence Impedance (ohms/1000') (ohms/1000') Positive Sequence Impedance (ohms/1000') (ohms/1000') Shield Short Circuit Current 6 Cycles Allowable Ampacity Directly Buried 90C Allowable Ampacity In Air 90C
More Options
2 AWG 2 AWG
0.162 0.24
0.221 0.33
0.028 0.04
0.024 0.04
0.577+j0.556 0.577+j0.556
0.221+j0.041 0.221+j0.041
1924 1924
201 201
172 172
More Options
1/0 AWG 1/0 AWG
0.102 0.15
0.139 0.21
0.024 0.04
0.021 0.03
0.503+j0.513 0.503+j0.513
0.139+j0.037 0.139+j0.037
2169 2169
257 257
225 225
More Options
2/0 AWG 2/0 AWG
0.082 0.12
0.112 0.17
0.022 0.03
0.020 0.03
0.479+j0.492 0.479+j0.492
0.112+j0.036 0.112+j0.036
2302 2302
292 292
260 260
More Options
250 KCMIL 250 KCMIL
0.043 0.06
0.059 0.09
0.017 0.03
0.017 0.03
0.430+j0.421 0.430+j0.421
0.059+j0.033 0.059+j0.033
2801 2801
410 410
376 376
More Options
350 KCMIL 350 KCMIL
0.031 0.05
0.043 0.06
0.014 0.02
0.015 0.02
0.412+j0.389 0.412+j0.389
0.043+j0.031 0.043+j0.031
3058 3058
487 487
460 460
More Options
500 KCMIL 500 KCMIL
0.021 0.03
0.030 0.04
0.012 0.02
0.014 0.02
0.394+j0.347 0.394+j0.347
0.030+j0.030 0.030+j0.030
3445 3445
573 573
556 556
More Options
750 KCMIL 750 KCMIL
0.014 0.02
0.021 0.03
0.011 0.02
0.013 0.02
0.370+j0.288 0.370+j0.288
0.021+j0.029 0.021+j0.029
4102 4102
668 668
678 678

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
* Ampacities are based on Table D17N of the Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
* Ampacities are based on Table D17E of the Canadian Electrical Code Part I
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)

Construction

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket