Southwire's Single Conductor 1kV Teck 90 is a CSA approved armoured cable for Industrial and Commercial applications. FT4, -40C, HL, AG14 and 90°C rated for use in harsh Canadian environments. Rated for installation in cable trays, duct banks, direct burial, troughs, hazardous locations, continuous rigid cable supports, and concrete encaseable. CSA AG14 Acid Gas compliance.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Drain Wire | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
80
2.03
|
55
1.40
|
1.221
3.10
|
13x14
13x14
|
45
1.14
|
1.311
3.33
|
1271
1891
|
1692
767.48
|
9.1
23.11
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
90
2.29
|
60
1.52
|
1.449
3.68
|
13x12
13x12
|
45
1.14
|
1.539
3.91
|
1935
2880
|
2800
1270.06
|
10.7
27.18
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
90
2.29
|
60
1.52
|
1.574
4.00
|
17x12
17x12
|
55
1.40
|
1.684
4.28
|
2579
3838
|
4000
1814.37
|
11.7
29.72
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
90
2.29
|
60
1.52
|
1.771
4.50
|
21x12
21x12
|
55
1.40
|
1.881
4.78
|
3572
5316
|
6000
2721.55
|
13.1
33.27
|
| More Options |
1000 KCMIL
1000 KCMIL
|
61
61
|
1.117
2.84
|
90
2.29
|
60
1.52
|
1.935
4.91
|
21x12
21x12
|
55
1.40
|
2.045
5.19
|
4480
6667
|
8000
3628.74
|
14.3
36.32
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
90
2.29
|
60
1.52
|
1.308
3.32
|
17x14
17x14
|
45
1.14
|
1.398
3.55
|
1507
2243
|
2000
907.18
|
9.7
24.64
|
* Other conductor sizes and outer jacket colours are available upon request. (#s in brackets represent # of strands / conductor. Number of strands may vary as per CSA standard.)
** Non-Standard sizes are available upon request. Reel sizes are not guaranteed. The factory reserves the right to make changes as necessary to optimize manufacturing requirements.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.062
0.09
|
0.041
0.06
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.039
0.06
|
0.040
0.06
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.029
0.04
|
0.039
0.06
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.022
0.03
|
0.038
0.06
|
| More Options |
1000 KCMIL
1000 KCMIL
|
0.011
0.02
|
0.018
0.03
|
0.037
0.06
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.053
0.08
|
0.041
0.06
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.