For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
14 AWG
14 AWG
|
7
7
|
0.070
0.18
|
45
1.14
|
1x14
1x14
|
65
1.65
|
0.690
1.75
|
45
1.14
|
0.780
1.98
|
279
415
|
131
59.42
|
5.4
13.72
|
| More Options |
12 AWG
12 AWG
|
7
7
|
0.088
0.22
|
45
1.14
|
1x14
1x14
|
65
1.65
|
0.775
1.97
|
45
1.14
|
0.865
2.20
|
354
527
|
208
94.35
|
6.0
15.24
|
| More Options |
10 AWG
10 AWG
|
7
7
|
0.113
0.29
|
45
1.14
|
1x12
1x12
|
65
1.65
|
0.723
1.84
|
45
1.14
|
0.813
2.07
|
303
451
|
166
75.30
|
5.6
14.22
|
| More Options |
10 AWG
10 AWG
|
7
7
|
0.113
0.29
|
45
1.14
|
1x12
1x12
|
65
1.65
|
0.833
2.12
|
45
1.14
|
0.923
2.34
|
435
647
|
332
150.59
|
6.4
16.26
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
| More Options |
14 AWG
14 AWG
|
2.631
3.92
|
3.170
4.72
|
0.058
0.09
|
| More Options |
12 AWG
12 AWG
|
1.662
2.47
|
2.002
2.98
|
0.054
0.08
|
| More Options |
10 AWG
10 AWG
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
| More Options |
10 AWG
10 AWG
|
1.040
1.55
|
1.253
1.86
|
0.050
0.07
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.