SPEC: 83043

Triplex 600 Volt RHH/RHW-2 or USE-2 AlumaFlex® Underground Service Entrance SPEC83043

Download Category Specifications
PDF Excel Table

Application & Features

Conductors are stranded, compressed aluminum Triple E AA8000 (8176-H24), insulated with cross-linked polyethylene Type RHH/RHW-2 or USE-2. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two-phase conductors and one neutral conductor are cabled together to produce the triplex cable configuration. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications

Select more options below for part numbers, packaging, and color options:
Code Word Cond. Size Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Diameter Over Insulation (in) (cm) Num x Neutral Size Neutral Stranding (mils) (mm) Neutral Insulation Thickness Ground Size Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
STEPHENS STEPHENS
2 AWG 2 AWG
7 7
0.283 0.72
63 1.60
0.409 1.04
4 4
6 0.15
60 60
AWG AWG
0.883 2.24
262 390
More Options
SWEETBRIAR SWEETBRIAR
4/0 AWG 4/0 AWG
18 18
0.512 1.30
84 2.13
0.68 1.73
2/0 2/0
11 0.28
80 80
AWG AWG
1.439 3.66
743 1106
More Options
WESLEYAN WESLEYAN
350 KCMIL 350 KCMIL
30 30
0.661 1.68
100 2.54
0.861 2.19
4/0 4/0
17 0.43
80 80
KCMIL KCMIL
1.817 4.62
1169 1740

^ HI-SCORE: Medium Density Polyethylene Insulation
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Code Word Cond. Size Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity In Duct 90C
More Options
STEPHENS STEPHENS
2 AWG 2 AWG
3.5 8.89
1194 541.59
0.266 0.40
0.331 0.49
0.045 0.07
90/100 90/100
More Options
SWEETBRIAR SWEETBRIAR
4/0 AWG 4/0 AWG
7.2 18.29
3808 1727.28
0.084 0.13
0.105 0.16
0.041 0.06
180/205 180/205
More Options
WESLEYAN WESLEYAN
350 KCMIL 350 KCMIL
9.1 23.11
6300 2857.63
0.051 0.08
0.064 0.10
0.040 0.06
250/280 250/280

Notes:
1. Inductive reactance assumes cables are cradled in conduit, and the neutral is carrying no current.
2. Conductors assumed to be reverse lay stranded, compressed construction.
3. Phase spacing assumes cables are touching.
4. Resistances shown are for the phase conductors only.
5. Ampacities based upon 2023 NEC Table 310.16 Ampacities of Insulated Conductors with Not More Than Three Current-Carrying Conductors in Raceway, Cable, or Earth (Directly Buried)

Standards & References

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables

Construction

  1. Conductor:Conductors are stranded, compressed Triple E per ASTM 800 and 801
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 or USE-2
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)