SPEC: 83043

4/0 3EAL 600VUD TX SWEETBRIAR/YS/USE-2 1000 FT SPEC83043 37712701

Southwire #: 37712701

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Conductor Color
Packaging

Application & Features

Conductors are stranded, compressed aluminum Triple E AA8000 (8176-H24), insulated with cross-linked polyethylene Type RHH/RHW-2 or USE-2. Neutrals are identified by three yellow extruded stripes. Cables with “YES” neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two-phase conductors and one neutral conductor are cabled together to produce the triplex cable configuration. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications

Code Word SWEETBRIAR SWEETBRIAR
Cond. Size 4/0 AWG 4/0 AWG
Cond. Strands 18 18
Diameter Over Conductor (in) (cm) 0.512 1.30 inch cm
Insulation Thickness (mils) (mm) 84 2.13 mils mm
Diameter Over Insulation (in) (cm) 0.68 1.73 inch cm
Num x Neutral Size 2/0 2/0
Neutral Stranding (mils) (mm) 11 0.28 mils mm
Neutral Insulation Thickness 80 80
Ground Size AWG AWG
Approx. OD (inches) (cm) 1.439 3.66 inch cm
Approx. Weight (lbs/1000') (kgs/km) 743 1106 lbs/1000' kgs/km

^ HI-SCORE: Medium Density Polyethylene Insulation
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Standards & References

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • ICEA S-105-692 Standard For 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables

Construction

  1. Conductor:Conductors are stranded, compressed Triple E per ASTM 800 and 801
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 or USE-2
  3. Neutral:Cross Linked Polyethylene (XLPE) with three Yellow Extruded Stripes (YES)