AL 600V-UD DUPLEX

Aluminum Conductors. Cross-linked Polyethylene (XLP) Insulation.

Download Category Specifications
PDF Excel Table

Application

Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.

Specifications

Select a set of products below for more information:
Conductor Ground Wire
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Size (AWG) No. of Strands Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km) Allowable Ampacity
273540
2 2
8 AWG 8 AWG
7 7
60 1.52
522 13.28
63 94
273557
2 2
6 AWG 6 AWG
7 7
60 1.52
596 15.14
88 131
273565
2 2
4 AWG 4 AWG
7 7
60 1.52
689 17.51
125 187
270918
2 2
2 AWG 2 AWG
7 7
60 1.52
806 20.47
183 272

Standards & References

Southwire's duplex 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications:

  • B-230
  • B-231

Construction

Conductors are stranded, compressed 1350-H19, H16, or H26 aluminum, insulated with vulcanized interlinked polyethylene (VIP 1 ), Southwire's cross-linked polyethylene. Neutrals are triple yellow extruded stripe. Cables with "YES" neutrals have sequential footage markers. Conductors are durably surface printed for identification.

  • 1350