| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Color | Insulation Thickness (mils) (mm) | Approx. OD (in) (cm) | Copper Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
16 AWG
16 AWG
|
2
2
|
26
26
|
0.059
0.15
|
Black
Black
|
45
1.14
|
0.305
0.77
|
16
24
|
37
55
|
| More Options |
14 AWG
14 AWG
|
2
2
|
41
41
|
0.073
0.19
|
Black
Black
|
45
1.14
|
0.341
0.87
|
25
37
|
45
67
|
| More Options |
12 AWG
12 AWG
|
2
2
|
65
65
|
0.094
0.24
|
Black
Black
|
45
1.14
|
0.357
0.91
|
40
60
|
66
98
|
| More Options |
10 AWG
10 AWG
|
2
2
|
104
104
|
0.117
0.30
|
Black
Black
|
45
1.14
|
0.443
1.13
|
64
95
|
94
140
|
| Cond. Size | Conductor Number | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) |
|
16 AWG
16 AWG
|
2
2
|
4.487
6.68
|
5.406
8.05
|
|
1.2
3.05
|
|
14 AWG
14 AWG
|
2
2
|
2.814
4.19
|
3.391
5.05
|
65
29.48
|
1.4
3.56
|
|
12 AWG
12 AWG
|
2
2
|
1.774
2.64
|
2.137
3.18
|
104
47.17
|
1.4
3.56
|
|
10 AWG
10 AWG
|
2
2
|
1.111
1.65
|
1.339
1.99
|
166
75.30
|
1.8
4.57
|
* Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.