SPEC: 45268

AL 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free SPEC45268

Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
2/0 AWG 2/0 AWG
4 4
12 12
0.376 0.96
50 1.27
80 2.03
1.342 3.41
546 813
1064 1583
More Options
3/0 AWG 3/0 AWG
4 4
15 15
0.422 1.07
50 1.27
80 2.03
1.456 3.70
678 1009
1236 1839
More Options
300 KCMIL 300 KCMIL
4 4
21 21
0.569 1.45
60 1.52
110 2.79
1.924 4.89
130 193
1141 1698
2113 3144
More Options
500 KCMIL 500 KCMIL
4 4
34 34
0.735 1.87
60 1.52
115 2.92
2.351 5.97
1982 2950
3123 4648
More Options
500 KCMIL 500 KCMIL
4 4
35 35
0.735 1.87
60 1.52
110 2.79
2.415 6.13
2029 3019
3177 4728
More Options
600 KCMIL 600 KCMIL
4 4
35 35
0.813 2.07
80 2.03
110 2.79
2.545 6.46
2029 3019
3717 5532
More Options
750 KCMIL 750 KCMIL
4 4
58 58
0.908 2.31
70 1.78
140 3.56
2.925 7.43
3014 4485
4687 6975

* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
2/0 AWG 2/0 AWG
4 4
6.7 17.02
2555 1158.93
0.133 0.20
0.160 0.24
0.043 0.06
108 108
120 120
More Options
3/0 AWG 3/0 AWG
4 4
7.3 18.54
3221 1461.02
0.105 0.16
0.126 0.19
0.042 0.06
124 124
140 140
More Options
300 KCMIL 300 KCMIL
4 4
9.6 24.38
5760 2612.69
0.059 0.09
0.071 0.11
0.041 0.06
184 184
208 208
More Options
500 KCMIL 500 KCMIL
4 4
14.1 35.81
9600 4354.48
0.035 0.05
0.044 0.07
0.039 0.06
248 248
280 280
More Options
500 KCMIL 500 KCMIL
4 4
14.5 36.83
9600 4354.48
0.035 0.05
0.044 0.07
0.039 0.06
248 248
280 280
More Options
600 KCMIL 600 KCMIL
4 4
15.7 39.88
14400 6531.72
0.029 0.04
0.037 0.06
0.039 0.06
272 272
308 308
More Options
750 KCMIL 750 KCMIL
4 4
17.6 44.70
18000 8164.66
0.024 0.04
0.031 0.05
0.038 0.06
308 308
348 348

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

Construction

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Resources

There are no downloadable resources for this product.