SPEC: 44066

Southwire® Machine Flex® Power PVC THHN SPEC44066

90°C Wet or Dry. 600 Volts. Flexible Stranded Copper Conductor. PVC Insulation and Nylon Jacket (THHN/THWN-2). Oil & Gasoline Resistant. Sunlight Resistant. Rated UL VW-1 and CSA FT1 & FT4 Flame Resistant.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s Machine Flex® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. 1/0 AWG & larger rated for CT use.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Approx. OD (in) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
4 AWG 4 AWG
1 1
413 413
0.235 0.60
50 1.27
0.335 0.85
153 228
More Options
4/0 AWG 4/0 AWG
1 1
2109 2109
0.550 1.40
60 1.52
0.664 1.69
746 1110
More Options
250 KCMIL 250 KCMIL
1 1
627 627
0.605 1.54
70 1.78
0.747 1.90
857 1275
More Options
300 KCMIL 300 KCMIL
1 1
741 741
0.638 1.62
70 1.78
0.780 1.98
1024 1524
More Options
350 KCMIL 350 KCMIL
1 1
893 893
0.670 1.70
60 1.52
0.812 2.06
1172 1744
More Options
500 KCMIL 500 KCMIL
1 1
1221 1221
0.858 2.18
70 1.78
0.998 2.53
1641 2442
More Options
600 KCMIL 600 KCMIL
1 1
1480 1480
0.963 2.45
70 1.78
1.127 2.86
2033 3025
More Options
750 KCMIL 750 KCMIL
1 1
1850 1850
1.094 2.78
80 2.03
1.258 3.20
2569 3823

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
4 AWG 4 AWG
0.282 0.42
0.340 0.51
0.048 0.07
333 151.05
1.3 3.30
85 85
95 95
More Options
4/0 AWG 4/0 AWG
0.057 0.08
0.069 0.10
0.041 0.06
1692 767.48
2.6 6.60
230 230
260 260
More Options
250 KCMIL 250 KCMIL
0.047 0.07
0.057 0.08
0.041 0.06
2000 907.18
2.9 7.37
255 255
290 290
More Options
300 KCMIL 300 KCMIL
0.039 0.06
0.048 0.07
0.041 0.06
2400 1088.62
3.1 7.87
285 285
320 320
More Options
350 KCMIL 350 KCMIL
0.033 0.05
0.042 0.06
0.040 0.06
2800 1270.06
3.2 8.13
310 310
350 350
More Options
500 KCMIL 500 KCMIL
0.023 0.03
0.031 0.05
0.039 0.06
4000 1814.37
3.9 9.91
380 380
430 430
More Options
600 KCMIL 600 KCMIL
0.019 0.03
0.027 0.04
0.039 0.06
4800 2177.24
5.6 14.22
420 420
475 475
More Options
750 KCMIL 750 KCMIL
0.016 0.02
0.024 0.04
0.038 0.06
6000 2721.55
6.2 15.75
475 475
535 535

† Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
† Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Size (Strand) Black Red Brown Orange Yellow Gray Green Pink Purple Tan Gray/Purple Green/Yellow
4 (413) 4 (413)
672867 672867
674667
3 (525) 3 (525)
664229 664229
2 (665) 2 (665)
1 (836) 1 (836)
456258 456258
1/0 (1044) 1/0 (1044)
674668 674668
677368 677368
2/0 (1330) 2/0 (1330)
456257 456257
3/0 (1672) 3/0 (1672)
457120 457120
457121 457121
664217 664217
664220 664220
664223 664223
664226 664226
4/0 (2109) 4/0 (2109)
679607
456271 456271
456253 456253
456254 456254
456255 456255
456256 456256
679606 679606
250 (627) 250 (627)
649414
672218
672217
672219
673792 673792
673791 673791
677370 677370
300 (741) 300 (741)
672866 672866
674116
674117
674118
674120
674121
350 (893) 350 (893)
649415
138181 138181
674662
674664
674665
674666
652964 652964
672017 672017
500 (1221) 500 (1221)
648948
646978
646979
646980
646981
677701
456461
456462
456463
456464
646982 646982
600 (1480) 600 (1480)
649416
678431
678432
678434
678435
673748 673748
678436 678436
750 (1850) 750 (1850)
649549 649549
139016 139016
677721
677722
677723
677725 677725
671518 671518
677726 677726
1000 (2516) 1000 (2516)
674459 674459
671527 671527
671524 671524
671521 671521

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 758 Standard for Appliance Wiring Material Style 2463 (80C, 600V)
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661

Construction

  1. Conductor: 8 - 4/0 AWG: Class K, flexible stranded bare copper. 250 - 750 kcmil: Class I, flexible stranded bare copper
  2. Insulation: Polyvinyl Chloride (PVC) with Nylon sheath

Resources

There are no downloadable resources for this product.