Titan2™ Type HC is suitable for the following installations:
For extreme temperature environments
For the installation and protection of electrical conductors in circuits of 600 Volts nominal, or less.
Where the conditions of installation, operation, or maintenance require flexibility or protection from liquids, vapors, solids, or weather
Used in industrial and commercial applications for conveyors, blowers, cranes, air conditioners, machine tooling and lubrication equipment
Exposed or concealed installations
Applications requiring movement, crossover connections, or tight bends
Permitted for equipment grounding in sizes 3/8" through 1-1/4" in lengths not exceeding 6 feet per NEC 250.118(6)
For flexible connections to swimming pool, spa, and hot tub motors per NEC® 680.21(A)(3) & 680.42(A)(1)
Electric signs and outline lighting supply and secondary-circuit conductors per NEC® 600.7, 600.31 (1000 volts or less) & 600.32 (over 1000 volts)
Floating building feeders and services per NEC® 553.7
Boatyards & Marinas in accordance with NEC® 555.13
Cranes & Hoists in accordance with NEC® 610.11(C)
For Elevator, Dumbwaiters, Escalators, Moving Walks, Wheel Chair Lifts & Stairway Chair Lifts in accordance with NEC® 620.21 (where expressly permitted)
Under raised floors in information technology equipment conductors and cables in accordance with NEC® 645.5 (D) & 645.5(D)(2)
Service entrance in lengths up to six feet per NEC® 230.43(15)
Electric signs and outline lighting supply and secondary-circuit per NEC 600.31 (1000 Volts or less) & NEC 600.32 (over 1000 Volts)
Approved for use in lengths longer than 6 feet per NEC® 356.10(5)
Hazardous location:
Class I, Div. 2 - NEC® 501.10(B)(2) and 501.30(B)
Class II, Div. 1 and 2 - NEC® 502.10(A)(2) and 502.30(B) and NEC 502.10(B)(2)
Class III, Div. 1 and 2 - NEC® 503.10(A)(2) and 503.30(B) and NEC 503.10(A)(2)
Titan2™ Type HC Features
A protective combination of thermoplastic materials formed into a conduit/raceway which seals out water, liquids, abrasives, alcohol, coolants, corrosive fumes and gases, dirt, grease, mineral acids, non-concentrated fixed alkalines, petroleum oils, salt air and spray, and weather
Smooth interior for easy wire pulling
UV sunlight resistant jacket
Rated for temperature range of -30°C to 80°C , 60°C Oil (-22 to +176, 140°F Oil)
Accepts standard liquid-tight fittings for use with LFNC-B
Rated for direct burial applications including concrete encasement