SPEC: 45265

AL 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free SPEC45265

Type TC-ER Power Cable 600 or 1000 Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

Download Category Specifications
PDF Excel Table

Application & Features

Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Ground Size Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Aluminum Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km)
More Options
3/0 AWG 3/0 AWG
4 4
16 16
0.423 1.07
55 1.40
1x4 1x4
80 2.03
1.476 3.75
678 1009
1127 1677
More Options
4/0 AWG 4/0 AWG
4 4
19 19
0.475 1.21
55 1.40
1x2 1x2
80 2.03
1.601 4.07
868 1292
1357 2019
More Options
250 KCMIL 250 KCMIL
4 4
22 22
0.52 1.32
65 1.65
1x1 1x1
110 2.79
1.813 4.61
1031 1534
1694 2521
More Options
300 KCMIL 300 KCMIL
4 4
21 21
0.57 1.45
65 1.65
1x2 1x2
110 2.79
1.934 4.91
1205 1793
1921 2859
More Options
350 KCMIL 350 KCMIL
4 4
35 35
0.616 1.56
65 1.65
1x1/0 1x1/0
110 2.79
2.045 5.19
1433 2133
2216 3298
More Options
400 KCMIL 400 KCMIL
4 4
35 35
0.659 1.67
65 1.65
1x1 1x1
110 2.79
2.149 5.46
1602 2384
2434 3622
More Options
500 KCMIL 500 KCMIL
4 4
34 34
0.736 1.87
65 1.65
1x1 1x1
110 2.79
2.335 5.93
1983 2951
2890 4301
More Options
600 KCMIL 600 KCMIL
4 4
37 37
0.813 2.07
80 2.03
1x1 1x1
110 2.79
2.66 6.76
2363 3517
3756 5590
More Options
750 KCMIL 750 KCMIL
4 4
58 58
0.908 2.31
80 2.03
1x1/0 1x1/0
140 3.56
2.887 7.33
2955 4398
4262 6343

* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size Conductor Number Min. Bend Radius (in) (cm) Max Pull Tension (lbs) (kg) DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
More Options
3/0 AWG 3/0 AWG
4 4
7.4 18.80
4027 1826.61
0.105 0.16
0.131 0.19
0.042 0.06
124 124
140 140
More Options
4/0 AWG 4/0 AWG
4 4
8 20.32
5078 2303.34
0.084 0.13
0.105 0.16
0.041 0.06
144 144
164 164
More Options
250 KCMIL 250 KCMIL
4 4
9.1 23.11
6000 2721.55
0.070 0.10
0.087 0.13
0.041 0.06
164 164
184 184
More Options
300 KCMIL 300 KCMIL
4 4
9.7 24.64
7200 3265.86
0.059 0.09
0.071 0.11
0.041 0.06
184 184
208 208
More Options
350 KCMIL 350 KCMIL
4 4
12.3 31.24
8400 3810.17
0.051 0.08
0.064 0.10
0.040 0.06
200 200
224 224
More Options
400 KCMIL 400 KCMIL
4 4
12.9 32.77
9600 4354.48
0.044 0.07
0.055 0.08
0.040 0.06
216 216
244 244
More Options
500 KCMIL 500 KCMIL
4 4
14 35.56
12000 5443.10
0.036 0.05
0.045 0.07
0.039 0.06
248 248
280 280
More Options
600 KCMIL 600 KCMIL
4 4
16 40.64
14400 6531.72
0.030 0.04
0.038 0.06
0.039 0.06
272 272
308 308
More Options
750 KCMIL 750 KCMIL
4 4
17.3 43.94
18000 8164.66
0.023 0.03
0.030 0.04
0.038 0.06
308 308
348 348

* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.

Standards & References

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy

Construction

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket