Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Ground Size | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
3/0 AWG
3/0 AWG
|
4
4
|
16
16
|
0.423
1.07
|
55
1.40
|
1x4
1x4
|
80
2.03
|
1.476
3.75
|
678
1009
|
1127
1677
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
19
19
|
0.475
1.21
|
55
1.40
|
1x2
1x2
|
80
2.03
|
1.601
4.07
|
868
1292
|
1357
2019
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
22
22
|
0.52
1.32
|
65
1.65
|
1x1
1x1
|
110
2.79
|
1.813
4.61
|
1031
1534
|
1694
2521
|
| More Options |
300 KCMIL
300 KCMIL
|
4
4
|
21
21
|
0.57
1.45
|
65
1.65
|
1x2
1x2
|
110
2.79
|
1.934
4.91
|
1205
1793
|
1921
2859
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
35
35
|
0.616
1.56
|
65
1.65
|
1x1/0
1x1/0
|
110
2.79
|
2.045
5.19
|
1433
2133
|
2216
3298
|
| More Options |
400 KCMIL
400 KCMIL
|
4
4
|
35
35
|
0.659
1.67
|
65
1.65
|
1x1
1x1
|
110
2.79
|
2.149
5.46
|
1602
2384
|
2434
3622
|
| More Options |
500 KCMIL
500 KCMIL
|
4
4
|
34
34
|
0.736
1.87
|
65
1.65
|
1x1
1x1
|
110
2.79
|
2.335
5.93
|
1983
2951
|
2890
4301
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
37
37
|
0.813
2.07
|
80
2.03
|
1x1
1x1
|
110
2.79
|
2.66
6.76
|
2363
3517
|
3756
5590
|
| More Options |
750 KCMIL
750 KCMIL
|
4
4
|
58
58
|
0.908
2.31
|
80
2.03
|
1x1/0
1x1/0
|
140
3.56
|
2.887
7.33
|
2955
4398
|
4262
6343
|
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
3/0 AWG
3/0 AWG
|
4
4
|
7.4
18.80
|
4027
1826.61
|
0.105
0.16
|
0.131
0.19
|
0.042
0.06
|
124
124
|
140
140
|
| More Options |
4/0 AWG
4/0 AWG
|
4
4
|
8
20.32
|
5078
2303.34
|
0.084
0.13
|
0.105
0.16
|
0.041
0.06
|
144
144
|
164
164
|
| More Options |
250 KCMIL
250 KCMIL
|
4
4
|
9.1
23.11
|
6000
2721.55
|
0.070
0.10
|
0.087
0.13
|
0.041
0.06
|
164
164
|
184
184
|
| More Options |
300 KCMIL
300 KCMIL
|
4
4
|
9.7
24.64
|
7200
3265.86
|
0.059
0.09
|
0.071
0.11
|
0.041
0.06
|
184
184
|
208
208
|
| More Options |
350 KCMIL
350 KCMIL
|
4
4
|
12.3
31.24
|
8400
3810.17
|
0.051
0.08
|
0.064
0.10
|
0.040
0.06
|
200
200
|
224
224
|
| More Options |
400 KCMIL
400 KCMIL
|
4
4
|
12.9
32.77
|
9600
4354.48
|
0.044
0.07
|
0.055
0.08
|
0.040
0.06
|
216
216
|
244
244
|
| More Options |
500 KCMIL
500 KCMIL
|
4
4
|
14
35.56
|
12000
5443.10
|
0.036
0.05
|
0.045
0.07
|
0.039
0.06
|
248
248
|
280
280
|
| More Options |
600 KCMIL
600 KCMIL
|
4
4
|
16
40.64
|
14400
6531.72
|
0.030
0.04
|
0.038
0.06
|
0.039
0.06
|
272
272
|
308
308
|
| More Options |
750 KCMIL
750 KCMIL
|
4
4
|
17.3
43.94
|
18000
8164.66
|
0.023
0.03
|
0.030
0.04
|
0.038
0.06
|
308
308
|
348
348
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.