2/0-3 AWG AlumaFlex™ THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor.
| Conductor | Ground Wire | |||||||
| Size (AWG or kcmil) (mm2) | No. of Conductors | Stranding | Nom. OD (mils) (mm) | Nominal Total Weight (lbs/1000') (kgs/km) | Size (AWG) | Ground Size UOM | Conductor Colors | |
| More Options |
6 AWG
6 AWG
|
3
3
|
Stranded
Stranded
|
885
22.49
|
269
401
|
8
8
|
AWG
AWG
|
BLACK/WHITE/RED
BLACK/WHITE/RED
|
| More Options |
2 AWG
2 AWG
|
3
3
|
Stranded
Stranded
|
1087
27.62
|
451
671
|
6
6
|
AWG
AWG
|
BLACK/WHITE/RED
BLACK/WHITE/RED
|
| More Options |
1 AWG
1 AWG
|
3
3
|
Stranded
Stranded
|
1197
30.41
|
550
819
|
6
6
|
AWG
AWG
|
BLACK/WHITE/RED
BLACK/WHITE/RED
|
Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy meets or exceeds these requirements:
Southwire AlumaFlex™ Type MC Cable with Triple E™ Aluminum Alloy is constructed with Type THHN/THWN-2 conductors rated 90˚ C dry, and a bare equipment grounding conductor. Conductors are AlumaFlex™ AA-8000 series aluminum alloy compact stranded. A binder tape is wrapped over the conductors. Aluminum interlocking armor is applied over the assembly. Conductors also available in High Voltage Colors.