Southwire’s 5kV 133% /8KV 100% cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), aerially supported by a messenger and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -25°C for cold bend and cold impact. Marked with "LTDD" CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemicals, oils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
2 AWG
2 AWG
|
7
7
|
0.282
0.72
|
0.545
1.38
|
115
2.92
|
0.605
1.54
|
55
1.40
|
0.755
1.92
|
454
676
|
530
240.40
|
9.0
22.86
|
2.5
6.35
|
| More Options |
1 AWG
1 AWG
|
19
19
|
0.322
0.82
|
0.590
1.50
|
115
2.92
|
0.650
1.65
|
55
1.40
|
0.800
2.03
|
527
784
|
669
303.45
|
9.6
24.38
|
2.5
6.35
|
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
0.630
1.60
|
115
2.92
|
0.690
1.75
|
80
2.03
|
0.870
2.21
|
639
951
|
844
382.83
|
10.4
26.42
|
2.5
6.35
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.674
1.71
|
115
2.92
|
0.734
1.86
|
80
2.03
|
0.914
2.32
|
745
1109
|
1064
482.62
|
10.9
27.69
|
3.0
7.62
|
| More Options |
3/0 AWG
3/0 AWG
|
19
19
|
0.456
1.16
|
0.724
1.84
|
115
2.92
|
0.784
1.99
|
80
2.03
|
0.964
2.45
|
877
1305
|
1342
608.72
|
11.5
29.21
|
3.0
7.62
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
0.780
1.98
|
115
2.92
|
0.840
2.13
|
80
2.03
|
1.020
2.59
|
1039
1546
|
1692
767.48
|
12.2
30.99
|
3.0
7.62
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
0.818
2.08
|
115
2.92
|
0.878
2.23
|
80
2.03
|
1.058
2.69
|
1179
1755
|
2000
907.18
|
12.6
32.00
|
3.0
7.62
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
0.937
2.38
|
115
2.92
|
0.997
2.53
|
80
2.03
|
1.177
2.99
|
1548
2304
|
2800
1270.06
|
14.1
35.81
|
3.5
8.89
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.042
2.65
|
115
2.92
|
1.102
2.80
|
80
2.03
|
1.282
3.26
|
2063
3070
|
4000
1814.37
|
15.3
38.86
|
4.0
10.16
|
| More Options |
600 KCMIL
600 KCMIL
|
61
61
|
0.865
2.20
|
1.152
2.93
|
115
2.92
|
1.212
3.08
|
80
2.03
|
1.392
3.54
|
2431
3618
|
4800
2177.24
|
16.7
42.42
|
4.0
10.16
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.254
3.19
|
115
2.92
|
1.314
3.34
|
80
2.03
|
1.494
3.79
|
2946
4384
|
6000
2721.55
|
17.9
45.47
|
4.5
11.43
|
| More Options |
1000 KCMIL
1000 KCMIL
|
61
61
|
1.117
2.84
|
1.403
3.56
|
115
2.92
|
1.463
3.72
|
80
2.03
|
1.643
4.17
|
3793
5645
|
8000
3628.74
|
19.7
50.04
|
5.0
12.70
|
* Conduit size based on 3 phase 40% fill-factor without ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
2 AWG
2 AWG
|
0.162
0.24
|
0.204
0.30
|
0.034
0.05
|
0.044
0.07
|
0.346 + j0.234
0.346 + j0.234
|
0.024 + j0.037
0.024 + j0.037
|
1920
1920
|
145
145
|
155
155
|
190
190
|
215
215
|
| More Options |
1 AWG
1 AWG
|
0.128
0.19
|
0.162
0.24
|
0.031
0.05
|
0.042
0.06
|
0.347 + j0.219
0.347 + j0.219
|
0.034 + j0.040
0.034 + j0.040
|
2044
2044
|
170
170
|
180
180
|
225
225
|
250
250
|
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.128
0.19
|
0.028
0.04
|
0.042
0.06
|
0.348 + j0.214
0.348 + j0.214
|
0.040 + j0.043
0.040 + j0.043
|
2165
2165
|
195
195
|
210
210
|
260
260
|
290
290
|
| More Options |
2/0 AWG
2/0 AWG
|
0.081
0.12
|
0.102
0.15
|
0.026
0.04
|
0.040
0.06
|
0.348 + j0.230
0.348 + j0.230
|
0.027 + j0.035
0.027 + j0.035
|
2302
2302
|
220
220
|
235
235
|
300
300
|
330
330
|
| More Options |
3/0 AWG
3/0 AWG
|
0.064
0.10
|
0.081
0.12
|
0.024
0.04
|
0.039
0.06
|
0.348 + j0.230
0.348 + j0.230
|
0.027 + j0.036
0.027 + j0.036
|
2459
2459
|
250
250
|
270
270
|
345
345
|
385
385
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.065
0.10
|
0.021
0.03
|
0.038
0.06
|
0.351 + j0.227
0.351 + j0.227
|
0.034 + j0.039
0.034 + j0.039
|
2633
2633
|
290
290
|
310
310
|
400
400
|
445
445
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.056
0.08
|
0.020
0.03
|
0.037
0.06
|
0.348 + j0.234
0.348 + j0.234
|
0.027 + j0.040
0.027 + j0.040
|
2800
2800
|
320
320
|
345
345
|
445
445
|
495
495
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.041
0.06
|
0.018
0.03
|
0.035
0.05
|
0.349 + j0.245
0.349 + j0.245
|
0.020 + j0.034
0.020 + j0.034
|
3120
3120
|
385
385
|
415
415
|
550
550
|
615
615
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.015
0.02
|
0.033
0.05
|
0.350 + j0.246
0.350 + j0.246
|
0.020 + j0.033
0.020 + j0.033
|
3516
3516
|
470
470
|
505
505
|
695
695
|
775
775
|
| More Options |
600 KCMIL
600 KCMIL
|
0.018
0.03
|
0.026
0.04
|
0.014
0.02
|
0.033
0.05
|
0.464 + j0.490
0.464 + j0.490
|
0.102 + j0.041
0.102 + j0.041
|
3782
3782
|
505
505
|
544
544
|
777
777
|
865
865
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.023
0.03
|
0.013
0.02
|
0.032
0.05
|
0.351 + j0.227
0.351 + j0.227
|
0.034 + j0.040
0.034 + j0.040
|
4102
4102
|
585
585
|
630
630
|
900
900
|
1000
1000
|
| More Options |
1000 KCMIL
1000 KCMIL
|
0.011
0.02
|
0.019
0.03
|
0.011
0.02
|
0.031
0.05
|
0.350 + j0.246
0.350 + j0.246
|
0.020 + j0.033
0.020 + j0.033
|
4563
4563
|
670
670
|
720
720
|
1075
1075
|
1200
1200
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.