Southwire’s 25KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
0.920
2.34
|
260
6.60
|
0.980
2.49
|
80
2.03
|
1.160
2.95
|
892
1327
|
844
382.83
|
13.9
35.31
|
3.5
8.89
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.964
2.45
|
260
6.60
|
1.024
2.60
|
80
2.03
|
1.204
3.06
|
1010
1503
|
1064
482.62
|
14.4
36.58
|
3.5
8.89
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
1.056
2.68
|
260
6.60
|
1.116
2.83
|
80
2.03
|
1.296
3.29
|
1318
1961
|
1692
767.48
|
15.5
39.37
|
4.0
10.16
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
1.108
2.81
|
260
6.60
|
1.168
2.97
|
80
2.03
|
1.348
3.42
|
1476
2197
|
2000
907.18
|
16.1
40.89
|
4.0
10.16
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.332
3.38
|
260
6.60
|
1.392
3.54
|
80
2.03
|
1.572
3.99
|
2409
3585
|
4000
1814.37
|
18.8
47.75
|
4.5
11.43
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.544
3.92
|
260
6.60
|
1.604
4.07
|
110
2.79
|
1.844
4.68
|
3443
5124
|
6000
2721.55
|
22.1
56.13
|
5.5
13.97
|
* Conduit size based on 3 phase 40% fill-factor without ground
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity In Duct 90C | Allowable Ampacity In Duct 105C | Allowable Ampacity In Air 90C | Allowable Ampacity In Air 105C | |
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.128
0.19
|
0.048
0.07
|
0.048
0.07
|
0.492 + j0.357
0.492 + j0.357
|
0.129 + j0.049
0.129 + j0.049
|
3064
3064
|
200
200
|
215
215
|
260
260
|
290
290
|
| More Options |
2/0 AWG
2/0 AWG
|
0.081
0.12
|
0.102
0.15
|
0.045
0.07
|
0.047
0.07
|
0.463 + j0.341
0.463 + j0.341
|
0.103 + j0.047
0.103 + j0.047
|
3200
3200
|
230
230
|
245
245
|
300
300
|
330
330
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.065
0.10
|
0.038
0.06
|
0.043
0.06
|
0.417 + j0.306
0.417 + j0.306
|
0.066 + j0.044
0.066 + j0.044
|
3532
3532
|
295
295
|
315
315
|
395
395
|
445
445
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.056
0.08
|
0.036
0.05
|
0.042
0.06
|
0.403 + j0.29
0.403 + j0.29
|
0.057 + j0.042
0.057 + j0.042
|
3699
3699
|
325
325
|
345
345
|
440
440
|
490
490
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.030
0.04
|
0.028
0.04
|
0.038
0.06
|
0.355 + j0.234
0.355 + j0.234
|
0.031 + j0.038
0.031 + j0.038
|
4415
4415
|
465
465
|
500
500
|
680
680
|
755
755
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.023
0.03
|
0.024
0.04
|
0.037
0.06
|
0.329 + j0.199
0.329 + j0.199
|
0.024 + j0.036
0.024 + j0.036
|
5000
5000
|
565
565
|
610
610
|
870
870
|
970
970
|
* NEC ampacities are based on:
* For Duct: Table 310.60(C)(11) Detail 1.
* For Free Air: Table 310.60(C)(3).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center..
* Capacitive Reactance is between Phase-to-Shield.