Southwire 2400V No Lead NL-EPR/SOLONON Traction Power Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO jacket. Meets Flame Spread and Smoke Release requirements of NFPA 130. Rated for 1000 lb/ft maximum sidewall pressure.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | |
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
125
3.18
|
80
2.03
|
0.826
2.10
|
568
845
|
845
383.29
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
125
3.18
|
80
2.03
|
0.871
2.21
|
671
999
|
1065
483.08
|
| More Options |
3/0 AWG
3/0 AWG
|
19
19
|
0.456
1.16
|
125
3.18
|
95
2.41
|
0.955
2.43
|
830
1235
|
1342
608.72
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
125
3.18
|
95
2.41
|
0.995
2.53
|
978
1455
|
1693
767.93
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
140
3.56
|
110
2.79
|
1.112
2.82
|
1179
1755
|
2000
907.18
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
140
3.56
|
110
2.79
|
1.207
3.07
|
1531
2278
|
2800
1270.06
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
140
3.56
|
110
2.79
|
1.322
3.36
|
2039
3034
|
4000
1814.37
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
155
3.94
|
125
3.18
|
1.611
4.09
|
3038
4521
|
6000
2721.55
|
| More Options |
1000 KCMIL
1000 KCMIL
|
61
61
|
1.117
2.84
|
155
3.94
|
125
3.18
|
1.761
4.47
|
3893
5793
|
8000
3628.74
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | |
| More Options |
1/0 AWG
1/0 AWG
|
| More Options |
2/0 AWG
2/0 AWG
|
| More Options |
3/0 AWG
3/0 AWG
|
| More Options |
4/0 AWG
4/0 AWG
|
| More Options |
250 KCMIL
250 KCMIL
|
| More Options |
350 KCMIL
350 KCMIL
|
| More Options |
500 KCMIL
500 KCMIL
|
| More Options |
750 KCMIL
750 KCMIL
|
| More Options |
1000 KCMIL
1000 KCMIL
|
* NEC ampacities are based on:
For Duct: Table 310.60(C)(77) Detail 1.
For Free Air: Table 310.60(C)(69).
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft, Spacing: one diameter spacing center-to-center.
* Capacitive Reactance is between Phase-to-Shield.