SPEC: 13068

Multi Conductor CL3R/FPLR Shielded SPEC13068

300V, 75°C, Multi-Conductor, Shielded, Stranded Copper, CL3R/FPLR

Download Category Specifications
PDF Excel Table

Application & Features

For use in Remote Control, Signaling, and Power-Limited circuits per NEC Article 725. Sizes 22 AWG - 16 AWG can also be used as communication circuits per NEC Article 800. Can be used in security, sound and audio, speaker cable, public address, intercom, sound reinforcement, alarm and access control circuits and power-limited controls. The conductors are cabled together; lay length varies depending on conductor count and gauge size.

  • Flame Test: UL 1666
  • Cable Type: CL3R, Also, CMR where UL permits (Sizes 16 AWG and smaller)
  • Voltage: 300 Volts
  • Temperature: 75ºC
  • Specifications

    Select a set of products below for more information:
    Cable Type Cond. Size Conductor Number Cond. Type Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (in) (cm) Copper Weight (lbs/1000') (kgs/km) Approx. Weight (lbs/1000') (kgs/km) Shield Type DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Allowable Ampacity Raceway 75C Allowable Ampacity Raceway 90C
    More Options
    CL3R/FPLR CL3R/FPLR
    14 AWG 14 AWG
    2 2
    CU CU
    19 19
    0.070 0.18
    10 0.25
    15 0.38
    0.218 0.55
    26 39
    36 54
    None None
    2.631 3.92
    3.170 4.72
    0.058 0.09
    20 20
    25 25
    More Options
    CL3R/FPLR CL3R/FPLR
    14 AWG 14 AWG
    4 4
    CU CU
    19 19
    0.070 0.18
    10 0.25
    15 0.38
    0.269 0.68
    52 77
    69 103
    None None
    2.631 3.92
    3.170 4.72
    0.058 0.09
    16 16
    20 20

    Standards & References

    • ASTM B8 Concentric-Lay-Stranded Copper Conductors
    • UL 13 Power-Limited Circuit Cables
    • UL 444 Communications Cables (90ºC, 300V)

    Construction

    1. Conductor:Stranded bare copper per ASTM B8
    2. Insulation:Polyvinyl Chloride (PVC)
    3. Shield:Aluminum foil shield with 24 AWG tinned drain wire
    4. Rip Cord:Rip cord for ease of jacket removal
    5. Jacket: Gray Polyvinyl Chloride (PVC)

    Resources