SPEC: 44103

4/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved SPEC44103

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

Download Category Specifications
PDF Excel Table

Application & Features

Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per Article NEC 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as perminant building wiring. Meets FT-5 Flame Test.

Specifications

Select more options below for part numbers, packaging, and color options:
Cond. Size Conductor Number Cond. Strands Diameter Over Conductor (in) (cm) Insulation Thickness (mils) (mm) Jacket Thickness (mils) (mm) Approx. OD (inches) (cm) Approx. Weight (lbs/1000') (kgs/km)
More Options
8 AWG 8 AWG
4 4
71 71
0.145 0.37
60 1.52
155 3.94
0.998 2.53
593 882
More Options
8 AWG 8 AWG
4 4
133 133
0.145 0.37
60 1.52
155 3.94
1.036 2.63
607 903
More Options
6 AWG 6 AWG
4 4
65 65
0.186 0.47
60 1.52
155 3.94
1.085 2.76
774 1152
More Options
4 AWG 4 AWG
4 4
112 112
0.235 0.60
60 1.52
165 4.19
1.227 3.12
1056 1572
More Options
2 AWG 2 AWG
4 4
168 168
0.291 0.74
60 1.52
180 4.57
1.453 3.69
1707 2540
More Options
1 AWG 1 AWG
4 4
224 224
0.3 0.76
80 2.03
155 3.94
1.617 4.11
1973 2936
More Options
1/0 AWG 1/0 AWG
4 4
259 259
0.379 0.96
80 2.03
175 4.45
1.718 4.36
2230 3319
More Options
2/0 AWG 2/0 AWG
4 4
324 324
0.4 1.02
80 2.03
210 5.33
1.872 4.75
2765 4115
More Options
3/0 AWG 3/0 AWG
4 4
418 418
0.48 1.22
80 2.03
210 5.33
1.986 5.04
3350 4985
More Options
4/0 AWG 4/0 AWG
4 4
532 532
0.53 1.35
80 2.03
220 5.59
2.174 5.52
3944 5869
More Options
350 KCMIL 350 KCMIL
4 4
893 893
0.67 1.70
95 2.41
375 9.53
2.877 7.31
7000 10417

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Cond. Size DC Resistance at 25C (ohms/1000') (ohms/km) AC Resistance at 75C (ohms/1000') (ohms/km) Inductive Reactance (ohms/1000') (ohms/km) Max Pull Tension (lbs) (kg) Min. Bend Radius (in) (cm) Allowable Ampacity In Air 60C Allowable Ampacity In Air 75C Allowable Ampacity In Air 90C
More Options
8 AWG 8 AWG
0.654 0.97
0.812 1.21
0.052 0.08
528 239.50
4 10.16
38 38
46 46
52 52
More Options
8 AWG 8 AWG
0.654 0.97
0.812 1.21
0.052 0.08
528 239.50
5.2 13.21
38 38
46 46
52 52
More Options
6 AWG 6 AWG
0.419 0.62
0.520 0.77
0.051 0.08
839 380.56
5.4 13.72
50 50
62 62
70 70
More Options
4 AWG 4 AWG
0.263 0.39
0.326 0.49
0.048 0.07
1335 605.55
6.1 15.49
67 67
81 81
91 91
More Options
2 AWG 2 AWG
0.166 0.25
0.206 0.31
0.045 0.07
2123 962.98
7.3 18.54
90 90
106 106
122 122
More Options
1 AWG 1 AWG
0.132 0.20
0.164 0.24
0.046 0.07
2678 1214.72
8.1 20.57
105 105
125 125
142 142
More Options
1/0 AWG 1/0 AWG
0.105 0.16
0.130 0.19
0.044 0.07
3379 1532.69
8.6 21.84
121 121
145 145
164 164
More Options
2/0 AWG 2/0 AWG
0.084 0.13
0.104 0.15
0.043 0.06
4259 1931.85
9.4 23.88
139 139
166 166
190 190
More Options
3/0 AWG 3/0 AWG
0.066 0.10
0.082 0.12
0.042 0.06
5369 2435.34
9.9 25.15
161 161
193 193
219 219
More Options
4/0 AWG 4/0 AWG
0.053 0.08
0.066 0.10
0.041 0.06
6771 3071.27
13 33.02
186 186
222 222
253 253
More Options
350 KCMIL 350 KCMIL
0.032 0.05
0.041 0.06
0.040 0.06
11200 5080.23
17.3 43.94
254 254
305 305
346 346

* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • CSA C22.2 No. 96 Portable Power Cables
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)

Construction

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red, green
  4. Fillers:Jute fillers applied as needed to round the cable core
  5. Reinforcement Binder:Reinforcing binder with twine applied over the core
  6. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)