Southwire’s RWU90 is designed for direct earth burial (with protection as required by the inspecting authority). For service entrance above or below ground. The minimum recommended installation temperature is minus 40°C (with suitable handling procedures). Maximum conductor temperature is 90°C. Note: Standard black is sunlight resistant and marked "SR". Standard coloured insulation is not sunlight resistant. SIMpull® technology on sizes #8 and larger. Cable can be installed in conduit without the aid of lubrication.
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Approx. OD (inches) (cm) | Aluminum Weight (lbs/1000') (kgs/km) | Approx. Weight (lbs/1000') (kgs/km) | |
| More Options |
6 AWG
6 AWG
|
1
1
|
7
7
|
0.169
0.43
|
70
1.78
|
0.339
0.86
|
24
36
|
55
82
|
| More Options |
4 AWG
4 AWG
|
1
1
|
7
7
|
0.212
0.54
|
70
1.78
|
0.383
0.97
|
39
58
|
76
113
|
| More Options |
2 AWG
2 AWG
|
1
1
|
6
6
|
0.268
0.68
|
70
1.78
|
0.438
1.11
|
62
92
|
106
158
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
18
18
|
0.336
0.85
|
95
2.41
|
0.536
1.36
|
99
147
|
162
241
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
12
12
|
0.376
0.96
|
95
2.41
|
0.576
1.46
|
125
186
|
194
289
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
15
15
|
0.422
1.07
|
95
2.41
|
0.623
1.58
|
158
235
|
234
348
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
19
19
|
0.474
1.20
|
95
2.41
|
0.675
1.71
|
199
296
|
283
421
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
22
22
|
0.520
1.32
|
110
2.79
|
0.752
1.91
|
235
350
|
342
509
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
35
35
|
0.615
1.56
|
110
2.79
|
0.848
2.15
|
329
490
|
453
674
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
34
34
|
0.735
1.87
|
110
2.79
|
0.970
2.46
|
471
701
|
616
917
|
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
37
37
|
0.812
2.06
|
108
2.74
|
1.077
2.74
|
565
841
|
747
1112
|
| More Options |
750 KCMIL
750 KCMIL
|
1
1
|
61
61
|
0.908
2.31
|
125
3.18
|
1.172
2.98
|
706
1051
|
907
1350
|
* Strand count meets minimum number per ASTM
| Cond. Size | Conductor Number | Min. Bend Radius (in) (cm) | Max Pull Tension (lbs) (kg) | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Allowable Ampacity Raceway 75C | Allowable Ampacity Raceway 90C | |
| More Options |
6 AWG
6 AWG
|
1
1
|
1.300
3.30
|
157
71.21
|
0.674
1.00
|
0.812
1.21
|
0.051
0.08
|
50
50
|
55
55
|
| More Options |
4 AWG
4 AWG
|
1
1
|
1.500
3.81
|
250
113.40
|
0.424
0.63
|
0.510
0.76
|
0.048
0.07
|
65
65
|
75
75
|
| More Options |
2 AWG
2 AWG
|
1
1
|
1.700
4.32
|
398
180.53
|
0.267
0.40
|
0.321
0.48
|
0.045
0.07
|
90
90
|
100
100
|
| More Options |
1/0 AWG
1/0 AWG
|
1
1
|
2.100
5.33
|
633
287.12
|
0.168
0.25
|
0.201
0.30
|
0.044
0.07
|
120
120
|
135
135
|
| More Options |
2/0 AWG
2/0 AWG
|
1
1
|
2.300
5.84
|
798
361.97
|
0.133
0.20
|
0.160
0.24
|
0.043
0.06
|
135
135
|
150
150
|
| More Options |
3/0 AWG
3/0 AWG
|
1
1
|
2.500
6.35
|
1006
456.31
|
0.105
0.16
|
0.126
0.19
|
0.042
0.06
|
155
155
|
175
175
|
| More Options |
4/0 AWG
4/0 AWG
|
1
1
|
2.700
6.86
|
1269
575.61
|
0.084
0.13
|
0.100
0.15
|
0.041
0.06
|
180
180
|
205
205
|
| More Options |
250 KCMIL
250 KCMIL
|
1
1
|
3.000
7.62
|
1500
680.39
|
0.071
0.11
|
0.086
0.13
|
0.041
0.06
|
205
205
|
230
230
|
| More Options |
350 KCMIL
350 KCMIL
|
1
1
|
3.400
8.64
|
2100
952.54
|
0.050
0.07
|
0.062
0.09
|
0.040
0.06
|
250
250
|
280
280
|
| More Options |
500 KCMIL
500 KCMIL
|
1
1
|
3.900
9.91
|
3000
1360.78
|
0.035
0.05
|
0.044
0.07
|
0.039
0.06
|
310
310
|
350
350
|
| More Options |
600 KCMIL
600 KCMIL
|
1
1
|
5.300
13.46
|
3600
1632.93
|
0.029
0.04
|
0.037
0.06
|
0.039
0.06
|
340
340
|
385
385
|
| More Options |
750 KCMIL
750 KCMIL
|
1
1
|
5.900
14.99
|
4500
2041.16
|
0.024
0.04
|
0.031
0.05
|
0.038
0.06
|
385
385
|
435
435
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.