Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
55
1.40
|
1.381
3.51
|
50
1.27
|
1.487
3.78
|
2058
3063
|
2703
1226.06
|
10.4
26.42
|
| More Options |
4/0 AWG
4/0 AWG
|
19
19
|
0.512
1.30
|
55
1.40
|
1.814
4.61
|
60
1.52
|
1.940
4.93
|
3773
5615
|
5416
2456.65
|
13.6
34.54
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
65
1.65
|
1.964
4.99
|
60
1.52
|
2.090
5.31
|
4343
6463
|
6400
2902.99
|
14.6
37.08
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
65
1.65
|
2.504
6.36
|
75
1.91
|
2.654
6.74
|
8284
12328
|
12800
5805.98
|
18.6
47.24
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.122
0.18
|
0.017
0.03
|
0.044
0.07
|
| More Options |
4/0 AWG
4/0 AWG
|
0.051
0.08
|
0.062
0.09
|
0.013
0.02
|
0.041
0.06
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.053
0.08
|
0.014
0.02
|
0.041
0.06
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.029
0.04
|
0.010
0.01
|
0.039
0.06
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.