Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Diameter Over Insulation (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Shield (in) (cm) | Inner Jacket Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Concentric Neutral | Jacket Thickness (mils) (mm) | Approx. OD (inches) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | Conduit Size (in) (cm) | |
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
0.884
2.25
|
220
5.59
|
0.944
2.40
|
80
2.03
|
1.424
3.62
|
7x12
7x12
|
50
1.27
|
1.524
3.87
|
1398
2080
|
1064
482.62
|
10.7
27.18
|
4
10.16
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
1.252
3.18
|
220
5.59
|
1.312
3.33
|
110
2.79
|
1.951
4.96
|
17x12
17x12
|
60
1.52
|
2.071
5.26
|
3215
4784
|
4000
1814.37
|
14.5
36.83
|
5.5
13.97
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
1.464
3.72
|
220
5.59
|
1.524
3.87
|
110
2.79
|
2.276
5.78
|
21x12
21x12
|
75
1.91
|
2.426
6.16
|
4625
6883
|
6000
2721.55
|
17
43.18
|
6.5
16.51
|
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | Zero Sequence Impedance (ohms/1000') (ohms/1000') | Positive Sequence Impedance (ohms/1000') (ohms/1000') | Shield Short Circuit Current 6 Cycles | Allowable Ampacity Directly Buried 90C | Allowable Ampacity In Air 90C | |
| More Options |
2/0 AWG
2/0 AWG
|
0.082
0.12
|
0.112
0.17
|
0.036
0.05
|
0.052
0.08
|
0.355+j0.127
0.355+j0.127
|
0.115+j0.057
0.115+j0.057
|
3879
3879
|
306
306
|
317
317
|
| More Options |
500 KCMIL
500 KCMIL
|
0.021
0.03
|
0.030
0.04
|
0.021
0.03
|
0.044
0.07
|
0.145+j0.039
0.145+j0.039
|
0.037+j0.048
0.037+j0.048
|
9420
9420
|
497
497
|
616
616
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.021
0.03
|
0.019
0.03
|
0.043
0.06
|
0.115+j0.031
0.115+j0.031
|
0.030+j0.045
0.030+j0.045
|
11636
11636
|
551
551
|
706
706
|
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on: