Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of op- erating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. The ground is sized to 50% of the phase conductor with three separate bare grounds one in each interstecie between condutors. Silicone Free.
| Cond. Size | Cond. Strands | Diameter Over Conductor (in) (cm) | Insulation Thickness (mils) (mm) | Diameter Over Armor (in) (cm) | Jacket Thickness (mils) (mm) | Approx. OD (in) (cm) | Approx. Weight (lbs/1000') (kgs/km) | Max Pull Tension (lbs) (kg) | Min. Bend Radius (in) (cm) | |
| More Options |
1/0 AWG
1/0 AWG
|
19
19
|
0.361
0.92
|
55
1.40
|
1.246
3.16
|
50
1.27
|
1.352
3.43
|
1677
2496
|
2534
1149.40
|
9.5
24.13
|
| More Options |
2/0 AWG
2/0 AWG
|
19
19
|
0.405
1.03
|
55
1.40
|
1.354
3.44
|
50
1.27
|
1.460
3.71
|
1983
2951
|
3194
1448.77
|
10.2
25.91
|
| More Options |
3/0 AWG
3/0 AWG
|
19
19
|
0.456
1.16
|
55
1.40
|
1.449
3.68
|
50
1.27
|
1.555
3.95
|
2524
3756
|
4027
1826.61
|
10.9
27.69
|
| More Options |
250 KCMIL
250 KCMIL
|
37
37
|
0.558
1.42
|
65
1.65
|
1.769
4.49
|
60
1.52
|
1.889
4.80
|
3597
5353
|
6000
2721.55
|
13.2
33.53
|
| More Options |
350 KCMIL
350 KCMIL
|
37
37
|
0.661
1.68
|
65
1.65
|
1.983
5.04
|
60
1.52
|
2.103
5.34
|
4780
7113
|
8400
3810.17
|
14.7
37.34
|
| More Options |
500 KCMIL
500 KCMIL
|
37
37
|
0.789
2.00
|
65
1.65
|
2.275
5.78
|
75
1.91
|
2.425
6.16
|
6629
9865
|
12000
5443.10
|
17.0
43.18
|
| More Options |
750 KCMIL
750 KCMIL
|
61
61
|
0.968
2.46
|
80
2.03
|
2.758
7.01
|
75
1.91
|
2.908
7.39
|
9751
14511
|
18000
8164.66
|
20.4
51.82
|
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
| Cond. Size | DC Resistance at 25C (ohms/1000') (ohms/km) | AC Resistance at 75C (ohms/1000') (ohms/km) | Capacitive Reactance (ohms/1000') (ohms/km) | Inductive Reactance (ohms/1000') (ohms/km) | |
| More Options |
1/0 AWG
1/0 AWG
|
0.102
0.15
|
0.122
0.18
|
0.017
0.03
|
0.044
0.07
|
| More Options |
2/0 AWG
2/0 AWG
|
0.081
0.12
|
0.097
0.14
|
0.016
0.02
|
0.043
0.06
|
| More Options |
3/0 AWG
3/0 AWG
|
0.064
0.10
|
0.078
0.12
|
0.014
0.02
|
0.042
0.06
|
| More Options |
250 KCMIL
250 KCMIL
|
0.043
0.06
|
0.053
0.08
|
0.014
0.02
|
0.041
0.06
|
| More Options |
350 KCMIL
350 KCMIL
|
0.031
0.05
|
0.039
0.06
|
0.012
0.02
|
0.040
0.06
|
| More Options |
500 KCMIL
500 KCMIL
|
0.022
0.03
|
0.029
0.04
|
0.010
0.01
|
0.039
0.06
|
| More Options |
750 KCMIL
750 KCMIL
|
0.014
0.02
|
0.022
0.03
|
0.010
0.01
|
0.038
0.06
|
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.