Conductors are stranded, compressed 1350-H16/H26 (3/4 Hard) aluminum, insulated with cross-linked polyethylene UL listed as Type USE-2 . These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
| Code Word | EMORY EMORY | |
| Cond. Size | 500 KCMIL 500 KCMIL | |
| Cond. Strands | 34 34 | |
| Diameter Over Conductor (in) (cm) | 0.789 2.00 | inch cm |
| Insulation Thickness (mils) (mm) | 95 2.41 | mils mm |
| Diameter Over Insulation (in) (cm) | 0.979 2.49 | inch cm |
| Ground Size | KCMIL KCMIL | |
| Approx. OD (inches) (cm) | 0.95 2.41 | inch cm |
| Approx. Weight (lbs/1000') (kgs/km) | 576 857 | lbs/1000' kgs/km |
1. The actual number of strands may differ for single input wire per ASTM B901
! Conductor is ASTM B901
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.