4/0 AL 600VUD QX WAKE FOREST/HISCORE/YS/USE-2 1000 FT

Southwire #: 30865001

Aluminum Conductors. Ruggedized XLP Insulation. Provides Superior Mechanical Protection.

Download Category Specifications
PDF Excel Table
Select Product Specifications
Construction
Packaging

Application

Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts. Especially suited for applications requiring superior resistance to mechanical damage. Rated 90°C continuous operation, 130°C emergency overload and short circuit 250°C.

Specifications

Stock # 30865001 30865001
No. of Conductors 4 4
Size (AWG or kcmil) (mm2) 4/0 AWG 4/0 AWG
No. of Strands 18 18
Nom. OD (mils) (mm) 1588 40.35 mils mm
Nominal Total Weight (lbs/1000') (kgs/km) 973 1449 lbs/1000' kgs/km

Standards & References

HI-SCORE quadruplex 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications:

  • B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
  • B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.

Construction

Conductors are stranded, compressed 1350-H16/H26 aluminum, insulated with a cross-linked polyethylene meeting the requirements of ANSI/ICEA S-81-570. Neutrals are triple yellow extruded stripe. Cables with "YES" neutrals have sequential footage markers. Conductors are durably surface printed for identification. Three phase conductors and one neutral conductor are cabled to produce the quadruplex cable configuration. Conductors are also available paralleled.

  • 1350