SPEC: 83248

Quadruplex XLPE Service Drop. ACSR Neutral - Messenger SPEC83248

Aluminum Conductors With Crosslinked Polyethylene Insulation.

Download Category Specifications
PDF Excel Table

Application & Features

Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures 90°C for crosslinked polyethylene (XLP) insulated conductors.

Specifications

Select more options below for part numbers, packaging, and color options:
Conductor
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
4 4
6 AWG 6 AWG
7 7
45 1.14
647 16.44
152 226
More Options
4 4
4 AWG 4 AWG
7 7
45 1.14
759 19.30
227 337
More Options
4 4
2 AWG 2 AWG
7 7
45 1.14
901 22.90
343 511
More Options
4 4
1/0 AWG 1/0 AWG
9 9
60 1.52
1139 28.94
551 820
More Options
4 4
2/0 AWG 2/0 AWG
11 11
60 1.52
1243 31.58
678 1009
More Options
4 4
3/0 AWG 3/0 AWG
17 17
60 1.52
1359 34.52
833 1240
More Options
4 4
4/0 AWG 4/0 AWG
18 18
60 1.52
1491 37.89
1034 1538
More Options
4 4
336.4 KCMIL 336.4 KCMIL
19 19
80 2.03
1944 49.39
1489 2215

^ Phase conductors have 0, 1, or 2 ribs for identification
1. The actual number of strands may differ for single input wire per ASTM B901
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Size Code Word OD (inches)
#6 #6
Turkey Turkey
0.198 0.198
#4 #4
Swan Swan
0.250 0.250
#2 #2
Sparrow Sparrow
0.316 0.316
1/0 1/0
Raven Raven
0.398 0.398
2/0 2/0
Quail Quail
0.447 0.447
3/0 3/0
Pigeon Pigeon
0.502 0.502
4/0 4/0
Penguin Penguin
0.684 0.684
336.4 336.4
Merlin Merlin
0.563 0.563

Standards & References

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ASTM B901 Standard Specification for Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction. (The number of strands for both phase and neutral may differ)
  • ICEA S-76-474 Standard for Neutral-Supported Power Cable Assemblies with Weather-Resistant Extruded Insulation Rated 600V

Construction

  1. Conductor:Conductors are stranded, compressed 1350-H19 aluminum
  2. Insulation:Cross Linked Polyethylene (XLPE)
  3. Messenger:ACSR Neutral

Resources

There are no downloadable resources for this product.