SPEC: 13005

Southwire CL4SS™ Class 4 Non-Shielded Outdoor / General Purpose SPEC13005

Download Category Specifications
PDF Excel Table

Application & Features

Intended for use in Fault Managed Power Systems (FMPS), remote powering, indoor Class 4 circuits per 2023 National Electrical Code (NEC) article 726. For use, primarily, in Agriculture, Intelligent Buildings, and Wireless Densification. The power source (transmitter) for Class 4 circuits shall be supplied from a power source that has a voltage output of 450 volts (peak or DC) or less. The CL4Z cables are considered for outdoor use only and are not to be attached to or used within a building structure. Type CL4Z cables comply with the applicable requirements for CL4. The CMG cables can be installed in buildings according to NEC article 722.135 and table 722.135(B).

Ratings:
Normal operating temperature: 90°C
Temperature Range: -40°C to 90°C
Rated Use: Dry or wet locations

Specifications

Select more options below for part numbers, packaging, and color options:
Conductor
No. of Conductors Size (AWG or kcmil) (mm2) No. of Strands Insulation Thickness (mils) (mm) Nom. OD (mils) (mm) Nominal Total Weight (lbs/1000') (kgs/km)
More Options
4 4
18 AWG 18 AWG
7 7
15 0.38
306 7.79
44 65
More Options
8 8
18 AWG 18 AWG
7 7
15 0.38
359 9.14
76 112
More Options
16 16
18 AWG 18 AWG
7 7
15 0.38
502 12.77
152 226
More Options
4 4
16 AWG 16 AWG
19 19
15 0.38
348 8.86
60 89
More Options
8 8
16 AWG 16 AWG
19 19
15 0.38
424 10.78
112 167
More Options
16 16
16 AWG 16 AWG
19 19
15 0.38
573 14.56
213 317
More Options
4 4
14 AWG 14 AWG
19 19
15 0.38
407 10.35
88 131
More Options
8 8
14 AWG 14 AWG
19 19
15 0.38
493 12.53
164 244
More Options
16 16
14 AWG 14 AWG
19 19
15 0.38
654 16.63
304 453

TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

Size
AWG
Capacitance
pF/ft
18 18
<30 <30
16 16
<30 <30
14 14
<30 <30
2 Pair
1 Black & Red
4 Pair
1 Black & Red
8 Pair
1 Black & Red
2 Black & White 2 Black & White
2 Black & White 2 Black & White
2 Black & White 2 Black & White
3 Black & Green 3 Black & Green
3 Black & Green 3 Black & Green
4 Black & Blue 4 Black & Blue
4 Black & Blue 4 Black & Blue
5 Black & Yellow 5 Black & Yellow
6 Black & Brown 6 Black & Brown
7 Black & Orange 7 Black & Orange
8 Black & White 8 Black & White

Standards & References

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1400-2 Fault-Managed Power Systems - Part 2: Requirements for Cables
  • UL 444 Communications Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test

Construction

  1. Conductor:Class B or C stranded soft-drawn bare copper per ASTM B3 and B8
  2. Insulation:Twisted pair(s) with premium grade, lead-free, flame-retardant, Polyvinyl Chloride (PVC). See Table 4 for pair(s) numbers and colors.
  3. Jacket:Lead-free, flame-retardant, LS, Polyvinyl Chloride (PVC). See Table 5 for available jacket colors.